GE AKD-10 Application Manual page 22

Hide thumbs Also See for AKD-10:
Table of Contents

Advertisement

.5 .6 .7 .8 .9 1
2
3
4
5
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
I
t
In
2
2
I
t
Out
1
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
.5 .6 .7 .8 .9 1
2
3
4
5
GE Consumer & Industrial -
Electrical Distribution
Available Ratings (Amperes)
Breaker
Current
Type
Model
Frame
Sensor (S) or CT
WP08
800
150, 400, 800
WP16
1600
800, 1600
LVPCB
WP20
2000
2000
WP32
3200
3200
WP40
4000
4000
WP50
5000
5000
Voltage Ratings: 600 Vac, nominal
05.07
MULTIPLES OF GROUND FAULT PICKUP SETTING
6 7 8 9 10
20
30
40
50 60 70 80 90
Max
Int
Min
6 7 8 9 10
20
30
40
50 60 70 8090
MULTIPLES OF GROUND FAULT PICKUP SETTING
Low-Voltage Power Circuit Breakers
Type WavePro
TM
with
Enhanced MicroVersaTrip Plus
MicroVersaTrip PM
TM
(Series RMS-9D),
or Power+
Digital RMS Trip Units
TM
Ground Fault Time-Current Curves
Curves apply at 50 to 60 Hertz
and from -20°C to 55°C breaker ambient.
-20°C to 70°C trip unit ambient.
Settings Glossary
S or CT = Current Sensor Rating in amps
DES-002B
MicroVersaTrip Plus & PM Adjustments
Ground Fault Function: Pickup settings in
TM
,
multiples of Current Sensor Rating (S)
Pickup Setting in
(S) or CT in Amps
Increments of .01
150 - 2000
.2 - .6
3200
.2 - .37
4000
.2 - .3
5000
.2 - .24
2
Delay Bands (I
t In & Out): 1 = Min, 2 = Int, 3 = Max
Power+ Adjustments
Ground Fault Function: Pickup settings in multiples of (S)
(S) In Amps
Current Sensor Rating
150 - 2000
.2, .25, .3, .35, .4, .45, .5, .6
3200
.2, .22, .24, .26, .28, .3, .34, .37
4000
.2, .22, .24, .26, .28, .30
2
Delay Bands (I
t In & Out): Min, Int, Max
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01