Viessmann VITODENS 200-W Service Instructions Manual page 89

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Repairs
(cont.)
3. Adjust value "9" with a or b;
confirm with d. The green ON
indicator flashes.
Access to the coding addresses of
the parameters is open.
4. Select the required coding address
with a or b (see the following
table) and change the value.
Coding
Coding in the delivered condition
Burner
7d:0
Air factor correction 0
82:0
Operation with natural
gas
83:15
Ignition start gas vo-
lume 15%
84:0
Start capacity correc-
tion 0 %
5. To exit, set the value of coding
address 11 9; then press L and
G simultaneously for approx. 1 s.
Coding has been terminated.
Note
If setting the parameters is not con-
cluded via coding address 11, the
system automatically terminates
the parameter change after approx.
25 min.
Possible change
7d: 5
Note
to
A change is only possible
7d:10
if manual calibration was
first carried out via cod-
ing address "85".
Air factor correction ad-
justable from
Each step represents an
air factor modification of
approx. 0.01.
82:1
Operation with LPG
83:0
Start gas volume adjusta-
to
ble from 0 to 31 %
83:31
84: 8
Start capacity correction
to
adjustable from -16 to
84:7
+14 %.
One step equals 2 %.
Troubleshooting
5 to 10.
89