Viessmann VITODENS 200-W Service Instructions Manual page 74

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
9C
X
X
9F
X
X
A2
X
A4
X
A7
X
74
System char-
Cause
acteristics
Control mode
Temperature
sensor lead
broken; con-
nects to the
Vitosolic at
S2
Control mode
Solar control
unit fault;
displayed if a
fault without
fault code
occurs at the
solar control
unit
Emergency
System
mode with
pressure too
system pres-
low
sure that is too
low, triggered
by code "0d"
(see page 42)
Control mode
Max. system
pressure ex-
ceeded
Control mode
Faulty pro-
as per deliv-
gramming
ered condition
unit.
Measures
Check the sensor
at the Vitosolic.
Check the solar
control unit (see
solar control unit
service instruc-
tions).
Top up with water
Check system
pressure.
Check the func-
tion and sizing of
the diaphragm ex-
pansion vessel.
Vent the heating
system.
Code "0E" is set
to 1 to document
the fault. After the
fault has been re-
moved, reset
manually to 0.
Replace the pro-
gramming unit.