Coding
Code 2
(cont.)
Coding in the delivered condition
67:40
With the Vitosolic:
Third set DHW tem-
perature = 40 °C
6F:...
Maximum output for
DHW heating in %, de-
faulted by the boiler
coding card
71:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
72:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
73:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
General
76:0
Without LON communi-
cation module (only for
weather-compensated
control units)
77 :1
LON subscriber number
(only for weather-com-
pensated control units)
48
Possible change
67:0
Without third set DHW
temperature
67:1
Third set DHW tempera-
to
ture adjustable from 1 to
67:60
60 °C (subject to the set-
ting of coding address
"56")
6F:0
Max. output during DHW
to
heating adjustable from 0
6F:100
to 100 %
71:1
"OFF" during DHW heat-
ing to the first set value
71:2
"ON" during DHW heat-
ing to the first set value
72:1
"OFF" during DHW heat-
ing to the second set
value
72:2
"ON" during DHW heat-
ing to the second set
value
73:1
during the time program
to
"ON" 1x/hour for 5 min
73:6
"ON" up to 6x/hour for
5 min
73:7
permanently "ON"
76:1
With LON communication
module; automatic recog-
nition
76:2
With KM BUS/cascade
communication module;
automatic recognition
77 :2
LON subscriber number,
to
adjustable from 1 to 99
77 :99
(see page 33).
Note
Allocate each number
only once.