Function description
Control functions
Filling with the control unit switched ON
If the system is to be filled with the
control unit switched ON, code "2F:2"
starts the pump.
Screed drying function
The screed function enables screeds
to be dried. For this, always observe
the details specified by the screed
manufacturer.
When the screed drying function is
activated, the heating circuit pump of
the mixer circuit is switched ON and
the flow temperature will be held at
the selected profile. After completion
(30 days), the mixer circuit will again
be regulated automatically via the set
parameters.
Observe EN 1264. The report to be
provided by the heating contractor
must contain the following heat-up
details:
Temperature profile 1: (EN 1264-4) code "F1:1"
100
(cont.)
The burner shuts down if this function
is enabled via coding address "2F".
The program is automatically disabled
after 20 min, and coding address "2F"
is set to "0".
Heat-up data with respective flow
temperatures
Max. flow temperature achieved
Operating condition and outside
temperature during handover
The various temperature profiles are
adjustable via coding address "F1".
The function continues after power
failure or after the control unit has
been switched OFF. "Heating and
DHW" will be started after the screed
drying function has been terminated
or if code "F1:0" is manually adjusted.