Viessmann VITODENS 200-W Service Instructions Manual page 77

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
CF
X
dA
X
db
X
dd
X
dE
X
E4
X
X
System char-
Cause
acteristics
Control mode
Communica-
tion fault,
LON com-
munication
module
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
shorted out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
with mixer
M2 shorted
out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
lead broken
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
with mixer
M2 lead bro-
ken
Burner
Supply vol-
blocked
tage fault
Troubleshooting
Measures
Replace the LON
communication
module.
Check the room
temperature sen-
sor, heating cir-
cuit A1.
Check the room
temperature sen-
sor, heating cir-
cuit with mixer
M2.
Check the room
temperature sen-
sor, heating cir-
cuit A1 and the
remote control
DIP switch set-
tings (see
page 104).
Check the room
temperature sen-
sor, heating cir-
cuit with mixer M2
and the remote
control DIP switch
settings (see
page 104).
Replace the con-
trol unit.