General Data - York TIWM006B21S Engineering Manual

Inverter-driven multi-split system heat pump air conditioners
Hide thumbs Also See for TIWM006B21S:
Table of Contents

Advertisement

WALL MOUNT

2.3 General Data

Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling Capacity
Nominal Heating Capacity
2
Sound Pressure Level
(Overall A Scale)
(Hi2-Hi-Me-Lo)
Outer Dimensions
Height
Width
Depth
Net Weight
Refrigerant
Indoor Fan
Airflow Rate
(Hi2-Hi-Me-Lo)
External Pressure
Motor Nominal Output
Connections
Refrigerant Piping
Liquid Line
Gas Line
Condensate Drain
OD
ID
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling Capacity
Nominal Heating Capacity
2
Sound Pressure Level
(Overall A Scale)
(Hi2-Hi-Me-Lo)
Outer Dimensions
Height
Width
Depth
Net Weight
Refrigerant
Indoor Fan
Airflow Rate
(Hi2-Hi-Me-Lo)
External Pressure
Motor Nominal Output
Connections
Refrigerant Piping
Liquid Line
Gas Line
Condensate Drain
OD
ID
1. Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
2. Sound pressure level is based on following conditions.
3.3 ft. (1m) Front of the Unit and 3.3 ft. (1m) Below the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
2-2
TIWM006B21S
1
Btu/h
6,000
(kW)
(1.8)
1
Btu/h
6,700
(kW)
(2.0)
39-35-32-30
dB
in. (mm)
11-13/16 (300)
in. (mm)
31-1/8 (790)
in. (mm)
9-1/16 (230)
lbs. (kg)
22 (10)
cfm
353-282-247-229
3
(10-8-7-6.5)
(m
/min.)
in.W.G
0.0
(Pa)
(0)
38
W
in. (mm)
1/4 (6.35)
in. (mm)
1/2 (12.70)
VP16
in. (mm)
7/8 (22)
in. (mm)
5/8 (16)
TIWM018B21S
1
Btu/h
18,000
(kW)
(5.3)
1
Btu/h
20,000
(kW)
(5.8)
dB
49-43-40-36
in. (mm)
13-1/8 (333)
in. (mm)
45-1/4 (1150)
in. (mm)
9-5/8 (245)
lbs. (kg)
37 (17)
cfm
671-600-494-424
3
(19-17-14-12)
(m
/min.)
in.W.G
0.0
(0)
(Pa)
38
W
in. (mm)
3/8 (9.52)
in. (mm)
5/8 (15.88)
VP16
in. (mm)
7/8 (22)
in. (mm)
5/8 (16)
80°F DB (26.7°C DB)
67°F WB (19.4°C WB)
Piping Lift: 0ft. (0m)
Wall Mount
TIWM008B21S
AC 1Phase, 208/230V, 60Hz
8,000
(2.3)
9,000
(2.6)
39-35-32-30
11-13/16 (300)
31-1/8 (790)
9-1/16 (230)
22 (10)
R410A
353-282-247-229
(10-8-7-6.5)
0.0
(0)
38
Flare-Nut Connection (with Flare Nuts)
1/4 (6.35)
1/2 (12.70)
VP16
7/8 (22)
5/8 (16)
Wall Mount
TIWM024B21S
AC 1Phase, 208/230V, 60Hz
24,000
(7.0)
27,000
(7.9)
51-49-46-41
13-1/8 (333)
45-1/4 (1150)
9-5/8 (245)
37 (17)
R410A
777-671-600-530
(22-19-17-15)
0.0
(0)
38
Flare-Nut Connection (with Flare Nuts)
3/8 (9.52)
5/8 (15.88)
VP16
7/8 (22)
5/8 (16)
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
TIWM015B21S
TIWM012B21S
12,000
15,000
(3.5)
13,500
17,000
(4.0)
46-40-36-33
42-40-38-33
11-13/16 (300)
13-1/8 (333)
35-7/16 (900)
45-1/4 (1150)
9-1/16 (230)
9-5/8 (245)
24 (11)
35 (16)
494-388-318-265
530-494-459-353
(14-11-9-7.5)
(15-14-13-10)
0.0
(0)
38
1/4 (6.35)
1/4 (6.35)
1/2 (12.70)
1/2 (12.70)
VP16
VP16
7/8 (22)
7/8 (22)
5/8 (16)
5/8 (16)
TIWM030B21S
30,000
(8.8)
34,000
(10.0)
51-49-46-41
13-1/8 (333)
45-1/4 (1150)
9-5/8 (245)
37 (17)
777-671-600-530
(22-19-17-15)
0.0
(0)
38
3/8 (9.52)
5/8 (15.88)
VP16
7/8 (22)
5/8 (16)
70°F DB (21.1°C DB)
43°F WB (6.1°C WB)
TC-17006-rev.1
(4.4)
(5.0)
0.0
(0)
38

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents