Operation
CAUTION
During startup insure that adequate gas
pressure is supplied to the main valves.
The indicator on the actuator should
never reach the bottom of the indicator
window. In the event that this happens,
adjustability will be lost. See minimum
incoming gas pressure requirement on
the test fire sheet. The SKP10 actuator
functions
only
as
activated, the indicator will reach the
bottom of the indication window. The
main gas pressure regulator is only
used
to
comply
with
regulations and therefore uses a high
outlet pressure spring that is set at the
max. The SKP70 fuel valves have a built
in regulator function.

Glossary of Terms

PRIMARY GAS
The smaller gas line injects fuel at the
burner head.
SECONDARY GAS
The main gas line inject fuel prior to the
burner head.
REVERSING ACTUATOR
Used for positioning control inlet damper,
combustion air.
AIR/GAS RATIO CONTROLLING
ACTUATOR
Regulates gas flow according to air
pressure.
32
VMP IOM
on/off.
When
standard
IMPORTANT
When commissioning this boiler, firing rate
must remain at low fire during first
4 hours of operation. The output may then
be increased 7% to 10% per hour, until a
firing rate of 75% is reached. The 75% firing
rate should be maintained for 3 to 4 hours.