Installation of outdoor

1 - 1 Introduction

This installation manual concerns VRV inverters of the Daikin RWEYQ-M series. These units are designed for indoor installation and used for cooling
and heatpump applications.
The RWEYQ-M units can be combined with Daikin VRV series indoor units for air conditioning purposes.
The present installation manual describes the procedures for unpacking, installing and connecting the RWEYQ-M units. Installation of the indoor units
is not described in this manual. Always refer to the installation manual supplied with these units for their installation.
1 - 1 - 1
Combination
The indoor units can be installed in the following range.
Always use appropriate indoor units compatible with R410A.
To lean which models of indoor units are compatible with R410A, refer to the product catalogs.
Total capacity/quantity of indoor units
<Outside unit > <Total capacity index of indoor units> <Total quantity of indoor units >
RWEYQ10MY1...................125 ~ 325
RWEYQ20MY1...................250 ~ 650
RWEYQ30MY1...................375 ~ 975
1 - 1 - 2

Standard operation limit

The figures below assume following operating conditions for indoor and outside units:
Equivalent pipe length ........................................ 7.5m
Level difference .................................................. 0m
Cooling
45
40
35
30
25
20
15
10
10
15
20
25
30
Indoor temperature (°CWB)
Operation range of water volume is 50-150L/min
Design in the following condition range
water temp. : 20-35°C
water volume : 60L/min more
When cooling condition load is small, thermostat-off may be carried out for freeze-up protection
Hold ambient temperature at 0-40°C
Heat rejection from the casing: 0.71kw/10HP
• Installation procedure
16 units
20 units
32 units
Heating
45
40
35
30
25
20
15
10
10
15
Indoor temperature (°CWB)
®
• VRV
Systems • Installation procedure
Range for continuous operation
Range for operation
Range for pull down operation
Range for warming up operation
20
25