The brine pump can be force controlled by connecting
a potential free switch function to the input selected in
menu 5.4, see page 51.
A closed switch means that the brine pump is active.
Contact for activation of "temporary lux"
An external switch function can be connected to F1155
for activation of the hot water function "temporary lux".
The switch must be potential-free and connected to the
selected input (menu 5.4, see page 51) on terminal block
X6 on the input board (AA3).
"temporary lux" is activated for the time that the contact
is connected.
Contact for activation of "economy"
An external switch function can be connected to F1155
to activate comfort mode "economy" for hot water op-
eration. The switch must be potential-free and connected
to the selected input (menu 5.4, see page 51) on terminal
block X6 on the input board (AA3).
Comfort mode "economy" is activated for the time that
the contact is connected.
Contact for activation of "external adjustment"
An external contact function can be connected to F1155
to change the supply temperature and the room temper-
ature.
When the switch is closed the temperature changes in
°C (if the room sensor is connected and activated). If a
room sensor is not connected or activated, the desired
change of "temperature" (heating curve offset) with the
number of steps selected is set. The value is adjustable
between -10 and +10.
climate system 1
The switch must be potential-free and connected to
the selected input (menu 5.4, see page 51) on terminal
block X6 on the input board (AA3).
The value for the change is set in menu 1.9.2, "external
adjustment".
climate system 2 to 8
External adjustment for climate systems 2 to 8 requires
accessories (ECS 40 or ECS 41).
See the accessory's installer handbook for installation
instructions.
Contact for activation of fan speed
Caution
The external contact function functions only if
the accessory FLM is installed and activated.
An external contact function can be connected to F1155
for activation of one of the four fan speeds. The switch
must be potential free and connected to the selected
input (menu 5.4, see page 51) on terminal block X6 on
the input circuit board (AA3). When the switch closes,
the selected fan speed is activated. Normal speed is re-
sumed when the contact is opened again.
28
Chapter 5 |
Electrical connections
NV 10, pressure/level/flow monitor brine
If the level sensor (accessory NV10) is desired for the
brine installation it can be connected on the selected
input (menu 5.4, see page 51) on terminal block X6 on
the input circuit board (AA3).
Pressure and flow sensors can also be connected to the
input.
The input must be closed during normal operation.
NIBE F1155