Crestron DIN-DALI-2 Programming Manual

Crestron DIN-DALI-2 Programming Manual

Din rail 2 channel dali interface
Hide thumbs Also See for DIN-DALI-2:

Advertisement

Crestron DIN-DALI-2
DIN Rail 2 Channel DALI Interface
Programming Guide

Advertisement

Table of Contents
loading

Summary of Contents for Crestron DIN-DALI-2

  • Page 1 Crestron DIN-DALI-2 DIN Rail 2 Channel DALI Interface Programming Guide...
  • Page 2: Table Of Contents

    Other trademarks, registered trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography.
  • Page 3: Din Rail 2 Channel Dali Interface: Din-Dali-2

    DALI related issues. It offers background information on the operation of the DIN-DALI-2, provides procedures for wiring tests and device replacement, and details the syntax and function of various advanced programming commands. Appendices offer reference materials about DALI protocol.
  • Page 4: Operation Of The Din-Dali-2

    The status of the ballast is also queried at a slower pace. This tells the DIN-DALI-2 if a lamp is out or if a ballast has just powered up. It also updates the DIN-DALI-2 internal list of connected ballasts. If a ballast is deemed not connected, it is polled at a much slower rate.
  • Page 5: Dali Wiring Considerations

    The levels and group information are also sent out whenever the DIN-DALI-2 unit powers up. The DIN-DALI-2 also stores a complete copy of all information that is stored in the individual ballasts, such as scene levels, groups, addresses, fade time, etc. This is...
  • Page 6: Ballast And Din-Dali-2 Replacement

    Crestron DIN-DALI-2 Ballast and DIN-DALI-2 Replacement The DIN-DALI-2 keeps a record of all ballasts it has commissioned, including all ballast settings such as fade times and groups. If a ballast fails and a replacement is installed, readdressing can take place from the front of the DIN-DALI-2 unit (no laptop necessary).
  • Page 7 (00 – 3F) and the new ballast starts flashing. Press and hold the applicable TEST button for 3 seconds to initiate reprogramming of the new ballast. Once the new ballast has been programmed, the DIN-DALI-2 returns to normal operation and displays its Cresnet ID. Replacing Multiple Ballasts To replace multiple ballasts, perform the following procedure for each affected loop.
  • Page 8: Din-Dali-2 Replacement

    Cresnet ID. DIN-DALI-2 Replacement The following process allows a failed DIN-DALI-2 controller to be replaced with a new unit. The ballast addresses and settings are extracted from the network and stored in the new DIN-DALI-2 controller.
  • Page 9: Advanced Dali Console Commands

    Multiple ballasts have not been addressed. They all have short addresses of 255 and long addresses of 0xFFFF and so only show up as one entry. Programming Guide – DOC. 7365A DIN Rail 2 Channel DALI Interface: DIN-DALI-2 • 7...
  • Page 10: Viewing The Din-Dali-2'S Stored Memory

    DALITEACHBYRND command. Viewing the DIN-DALI-2’s Stored Memory The DIN-DALI-2 unit stores a copy of the information that is stored in the ballast. It also stores records related to whether a ballast is connecting and reporting on the network and whether a ballast was ever commissioned.
  • Page 11 LISTBALCFG [LOOP] ALL COMMISSIONED The COMMISSIONED flag is 0 or 1. ⇒ 1: The ballast was commissioned and the DIN-DALI-2 expects to see it on the loop. If the ballast is not physically present, the DIN-DALI-2 reports it as missing and tries to replace the address during the ballast replacement process.
  • Page 12 This displays the minimum dim level that the ballasts can dim to. Note that the DIN-DALI-2 does not allow min to be set to a value less than 128. Even though this is half the useable dimming range it corresponds to a light level of ~3% based on logarithmic curve specified by DALI standards.
  • Page 13: Addressing Ballasts

    Constructing DALI Packets For lower level troubleshooting, the DIN-DALI-2 console allows raw DALI packets to be constructed and the responses displayed. If the response from the ballast must be displayed on the console, the debug console must first be enabled and standard polling of ballasts must be disabled.
  • Page 14 ADDRESS COMMAND SENDDALIPKT 1 0106 Short address 00 SENDDALIPKT 1 0D06 Short address 06 SENDDALIPKT 1 7F06 Short address 63 SENDDALIPKT 1 8306 Group address 01 12 • DIN Rail 2 Channel DALI Interface: DIN-DALI-2 Programming Guide – DOC. 7365A...
  • Page 15 Byte Equivalents for Short and Group Addresses SHORT ADDR SHORT ADDR SHORT ADDR SHORT ADDR GROUP ADDR ADDRESS BYTE ADDRESS BYTE ADDRESS BYTE ADDRESS BYTE ADDRESS BYTE Programming Guide – DOC. 7365A DIN Rail 2 Channel DALI Interface: DIN-DALI-2 • 13...
  • Page 16 • Bit 3 – 6: Ignore • Bit 7: Value of 0 means power is okay. Value of 1 means power cycled since last intensity command. 14 • DIN Rail 2 Channel DALI Interface: DIN-DALI-2 Programming Guide – DOC. 7365A...
  • Page 17: Clearing Out The Din-Dali-2 Internal Memory

    If this occurs, the internal memory in the DIN-DALI-2 should be cleared and the latest settings read back in from the ballasts. Both can be achieved using the software tool.
  • Page 18: Appendix A: Dali Protocol Summary

    If S = 0 the following data is interpreted as a power level with a value between 0x00 (off) and 0xFE (maximum power level). Standard commands are listed in the table beginning on the following page. 16 • DIN Rail 2 Channel DALI Interface: DIN-DALI-2 Programming Guide – DOC. 7365A...
  • Page 19 QUERY RESET STATE YAAAAAA1 10010110 QUERY MISSING SHORT ADDRESS YAAAAAA1 10010111 QUERY VERSION NUMBER YAAAAAA1 10011000 QUERY CONTENT DTR YAAAAAA1 10011001 QUERY DEVICE TYPE (Continued on following page) Programming Guide – DOC. 7365A DIN Rail 2 Channel DALI Interface: DIN-DALI-2 • 17...
  • Page 20 11000001 QUERY GROUPS 8–15 YAAAAAA1 11000010 QUERY RANDOM ADDRESS (H) YAAAAAA1 11000011 QUERY RANDOM ADDRESS (M) YAAAAAA1 11001100 QUERY RANDOM ADDRESS (L) 197–223 YAAAAAA1 10XXXXX RESERVED 18 • DIN Rail 2 Channel DALI Interface: DIN-DALI-2 Programming Guide – DOC. 7365A...
  • Page 21: Appendix B: Ballast Address To Hex Translation

    Refer to the following table when translating ballast address to hex addresses. Hex and Ballast Address Conversion Table BALLAST BALLAST BALLAST BALLAST ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS Programming Guide – DOC. 7365A DIN Rail 2 Channel DALI Interface: DIN-DALI-2 • 19...
  • Page 22: Glossary

    (half the original). If the DIN-DALI-2 does not hear a response then it retries with a higher value (in between the last two values). This process repeats until a single ballast is found—that is, when a response is heard after querying long...
  • Page 23 Crestron DIN-DALI-2 DIN Rail 2 Channel DALI Interface This page is intentionally left blank. Programming Guide – DOC. 7365A DIN Rail 2 Channel DALI Interface: DIN-DALI-2 • 21...
  • Page 24 Crestron Electronics, Inc. Programming Guide – DOC. 7365A (2034883) 15 Volvo Drive Rockleigh, NJ 07647 Tel: 888.CRESTRON 04.13 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.