Non-Directional Earth-Fault Protection (Efxptoc) - ABB REV615 Product Manual

Capacitor bank protection and control
Hide thumbs Also See for REV615:
Table of Contents

Advertisement

Capacitor Bank Protection and Control
REV615
Product version: 5.0 FP1
Table 29. Non-directional earth-fault protection (EFxPTOC)
Characteristic
Operation accuracy
Start time
1)2)
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Measurement mode = default (depends on stage), current before fault = 0.0 × I
1)
statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum
Start value = 2.5 × I
,
Start value multiples in range of 1.5...20
n
Table 30. Non-directional earth-fault protection (EFxPTOC) main settings
Parameter
Start value
Time multiplier
Operate delay time
1)
Operating curve type
1)
For further reference, see the Operation characteristics table
28
EFLPTOC
EFHPTOC
and
EFIPTOC
EFIPTOC:
Start value
I
= 2 × set
Fault
Start value
I
= 10 × set
Fault
EFHPTOC and EFLPTOC:
Start value
I
= 2 × set
Fault
, f
n
n
Function
EFLPTOC
EFHPTOC
EFIPTOC
EFLPTOC and EFHPTOC
EFLPTOC and EFHPTOC
EFIPTOC
EFLPTOC
EFHPTOC
EFIPTOC
Value
Depending on the frequency of the measured current: f
±1.5% of the set value or ±0.002 × I
±1.5% of set value or ±0.002 × I
(at currents in the range of 0.1...10 × I
±5.0% of the set value
(at currents in the range of 10...40 × I
Minimum
16 ms
11 ms
23 ms
Typically 40 ms
Typically 0.96
<30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n × f
Peak-to-Peak: No suppression
= 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on
Value (Range)
0.010...5.000 × I
n
0.10...40.00 × I
n
1.00...40.00 × I
n
0.05...15.00
40...200000 ms
20...200000 ms
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
1MRS757952 D
n
n
)
n
)
n
Typical
Maximum
19 ms
23 ms
12 ms
14 ms
26 ms
29 ms
3)
, where n = 2, 3, 4, 5,...
n
Step
0.005
0.01
0.01
0.01
10
10
±2 Hz
n
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 615 series

Table of Contents