Default Setting Values - Emerson XR75CX Installation And Operation Manual

Digital controller for medium-low temperature refrigeration applications
Table of Contents

Advertisement

19 Default Setting Values

Label
SEt
Setpoint
rtc*
Real time clock menu
Hy
Differential
LS
Minimum setpoint
US
Maximum setpoint
ot
Thermostat probe calibration
P2P
Evaporator probe presence
oE
Evaporator probe calibration
P3P
Third probe presence
o3
Third probe calibration
P4P
Fourth probe presence
o4
Fourth probe calibration
Ods
Outputs delay at start up
Ac
Anti-short cycle delay
rtr
P1-P2 percentage for regulation
CCt
Continuous cycle duration
CCS
Setpoint for continuous cycle
Con
Compressor ON time with faulty probe
CoF
Compressor OFF time with faulty probe
CF
Temperature measurement unit
rES
Resolution
Lod
Probe displayed
X-REP display
2
Red
dLy
Display temperature delay
dtr
P1-P2 percentage for display
EdF*
Kind of interval for defrost
tdF
Defrost type
dFP
Probe selection for defrost termination
dtE
Defrost termination temperature
IdF
Interval between defrost cycles
MdF
(Maximum) length for defrost
dSd
Start defrost delay
dFd
Displaying during defrost
dAd
MAX display delay after defrost
Fdt
Draining time
dPo
First defrost after start-up
dAF
Defrost delay after fast freezing
Table 19-1 - Default Setting Values (
MODBUS Termination Blocks
Name
*
Only for models with real time clock (RTC),
Range
LS to US
-
0.1 to 25.5°C/ 1 to 255°F
-100°C to SEt/-58°F to SEt
SEt to 110°C/ SEt to 230°F
-12 to 12°C /-120 to 120°F
n = not present; Y = present
-12 to 12°C /-120 to 120°F
n = not present; Y = present
-12 to 12°C /-120 to 120°F
n = not present; Y = present
-12 to 12°C /-120 to 120°F
0 to 255 min
0 to 50 min
0 to 100 (100 = P1, 0 = P2)
0.0 to 24.0 hr
(-100 to 150.0°C) (-67 to 302°F)
0 to 255 min
0 to 255 min
°C to °F
in = integer; dE = decimal point
P1; P2
P1 – P2 – P3 – P4 – SEt – dtr
0 to 20.0 min (10 sec)
1 to 99
rtC to in
EL = electric heater; in = hot gas
nP; P1; P2; P3; P4
-50 to 50°C
1 to 120 hr
0 to 255 min
0 to 99 min
rt, it, SEt, dEF
0 to 255 min
0 to 120 min
n = after IdF; y = immediately
0 to 23 hr and 50'
2
Only for XR75CX with X-REP output)
Value
Level
-5.0
---
-
Pr1
2.0
Pr1
-50.0
Pr2
110
Pr2
0.0
Pr1
Y
Pr1
0.0
Pr2
n
Pr2
0
Pr2
n
Pr2
0
Pr2
0
Pr2
1
Pr1
100
Pr2
0.0
Pr2
-5
Pr2
15
Pr2
30
Pr2
°C
Pr2
dE
Pr1
P1
Pr2
P1
Pr2
0.0
Pr2
50
Pr2
rtC
Pr2
EL
Pr1
P2
Pr2
8
Pr1
6
Pr1
30
Pr1
0
Pr2
it
Pr2
30
Pr2
0
Pr2
n
Pr2
0.0
Pr2
Default Setting Values • 27