4.4
System Connection Configuration
If possible, connect the XDO modules to XDPs or XDCs in an interlaced configuration (see
Figure 10). Interlacing the connection piping will keep half the XDP/XDC units operating and main-
tain even cooling in the conditioned space should one of the XDP or XDC units fail.
However, in a system with just one XDP or XDC, connect XDO modules in a non-interlaced configura-
tion (see Figure 11).
Figure 10 Typical XDO piping—interlaced connections
XDP/XDC A
Supply A
Return A
Return B
Supply B
XDP/XDC B
NOTE: Line size does NOT indicate pipe size difference.
Figure 11 Typical XDO piping—non-interlaced connection
Return
Supply
XDP/XDC
TOP VIEW—NOT TO SCALE
XDO A
XDO B
XDO B
XDO A
TOP VIEW—NOT TO SCALE
XDO A
XDO A
11