Honeywell N05 Series Product Data page 7

Non-spring return direct-coupled damper actuators for modulating and floating control
Table of Contents

Advertisement

N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
terminal
1
2
3
4
5
0[2]...10 V (feedback)
NOTE: All cables connected to these terminals must be equipped with spark suppression.
terminal
S1
common lead for switches A and B
S2, S3
change-over switch A (S1/S2 opens and S1/S3 closes when shaft adapter moves CW past 5°; reverts to
original state when shaft adapter moves CCW past 5°).
S5, S6
change-over switch B (S1/S5 opens and S1/S6 closes when shaft adapter moves CW past 85°; reverts to
original state when shaft adapter moves CCW past 85°).
Table 4. Signals at terminals
modulating
24 V ~/+ (power)
common ~/-
0[2]...10 V (control)
24 V ~/+ (override)
Table 5. Internal end switches
mode
floating
unused or (with feedback)
24 V ~/+ (power)
common ~/-
24 V ~/+ (control signal)
24 V ~/+ (control signal)
unused or (with feedback)
0...10 V
type of switch
7
2-position
unused or (with feedback)
24 V ~/+ (power)
common ~/-
24 V ~/+ (control signal)
24 V ~/+ (control signal)
unused or (with feedback)
0...10 V
63-6233T
CN0B-0545CH33 R0805