Occupancy Sensor OCS 100C • Setup Guide
The OCS 100C is a dual technology occupancy sensor that can be used to automate meeting and presentation spaces when
used with Extron control products. The OCS is equipped with ultrasonic (US), infrared (PIR), and photocell sensors that can be
used together to report ambient light conditions and room occupancy. Sensors can be wired directly to Extron controller products
equipped with Digital I/Os ports or via eBUS, when using optional eBUS interface accessories.
The OCS requires 24 VDC for operation. If local 24 V power is not available, use the included 12 V to 24 V power converter.
NOTE:
The OCS 100C is designed to detect occupancy using both the PIR and US sensors with their default settings to
avoid false detections.
Front Panel Features and Control
Ultrasonic
Ultrasonic
Sensors
Sensors
Figure 1.
OCS 100C Front Panel Features
Ultrasonic sensors (4) — Detect movement in the room, based on ultrasonic sound waves. The US sensor emits ultrasonic
sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are
caused by the movement of people, which is detected by the US waves.
Ultrasonic (US) Green LED status indicators (2) — Flash when the ultrasonic sensors detect occupancy.
Fresnel lens — Diffracts the incoming light and directs the light to the infrared sensor.
Retainer Ring — Holds the optional IR mask in place. Remove to access all controls and DIP switches. Insert the flat end of
a small screwdriver into the notch in the retainer ring to lever it up and off.
Infrared (PIR) Red LED status indicator — Located behind the fresnel lens, these LEDs flash when the infrared sensor
detects occupancy.
Infrared Sensor — The infrared (PIR) sensor detects the presence of people based on the difference between the heat
generated by moving people versus the ambient room temperature.
DIP Switches A —
A
Switch Function
1
Not used
2
Occupancy
detection
behavior - Dual
technology mode
3
Sensor status
indicators
4
Automatic adjust
reset
*Default and recommended settings
Ultrasonic (US)
Ultrasonic (US)
Green LED
Green LED
(status indicator)
(status indicator)
Fresnel Lens
Fresnel Lens
Retainer Ring
Retainer Ring
Ultrasonic (US)
Ultrasonic (US)
Green LED
Green LED
(status indicator)
(status indicator)
OFF
ON
*Not used
Not used
*Mutually
Independent
exclusive
(either PIR or US
(requires both
detection)
PIR and US
detection
*LEDs enabled
LEDs disabled
*Retain
Erase all learned
learned sensor
settings (toggle
adjustments
ON, then OFF)
Infrared (PIR)
Infrared (PIR)
Red LED
Red LED
(status indicator)
(status indicator)
DIP Switches (A)
)
DIP Switches (A)
)
Red Infrared
Red Infrared
Sensitivity Dial
A
A
Sensitivity Dial
1
2
3
4
Black Timer
ON
Black Timer
Dial
Dial
Figure 2.
OCS 100C Controls
Switch is not used.
If A2 is set to OFF, both the PIR and US sensors must
be triggered (simultaneously) before the OCS reports an
occupancy signal. If A2 is set to ON, the OCS reports
occupancy based on only one of the sensors being
triggered. When only one sensor is desired, set A2 to ON
and adjust the dials accordingly. If A2 is ON, false detection
when the room is not occupied increases.
Setting A3 to OFF provides a visual notification whenever
the PIR or US sensors are triggered. When the visual LED
indicators are a distraction or you want to disable the
flashing LEDs, A3 should be set to ON.
Only applicable when Timer (B3) or Sensitivity adjust (B4) or
both are set to Automatic mode (OFF). Toggling A4 ON then
OFF will reset any stored learned adjustments.
Infrared Sensor
Infrared Sensor
DIP Switches (B)
DIP Switches (B)
Green Ultrasonic
B
Green Ultrasonic
Sensitivity Dial
B
1
1
Sensitivity Dial
2
1
2
2
3
3
4
3
4
4
ON
ON
ON
Blue Photocell
Blue Photocell
Sensitivity Dial
Sensitivity Dial
Note
1

Advertisement

Table of Contents
loading

Summary of Contents for Extron electronics OCS 100C

  • Page 1 Occupancy Sensor OCS 100C • Setup Guide The OCS 100C is a dual technology occupancy sensor that can be used to automate meeting and presentation spaces when used with Extron control products. The OCS is equipped with ultrasonic (US), infrared (PIR), and photocell sensors that can be used together to report ambient light conditions and room occupancy.
  • Page 2 Occupancy Sensor OCS 100C • Setup Guide (Continued) • DIP Switches B — (see figure 2 on the previous page) Switch Function Note *Disabled High Airflow Enabled If enabled (set to ON) the sensor will not detect minor changes compensator and movement. This could result in missed detection, with a low trigger-on threshold.
  • Page 3: Recommended Setup

    Automatic Mode Out of the box, the OCS 100C can be setup in Automatic Mode, where no manual sensitivity adjustments are needed and sensitivity learning and adjustments are made automatically. For simple setup, we recommend keeping the OCS in the default settings and flipping the B4 Dip switch to the OFF (Auto) position.
  • Page 4 Occupancy Sensor OCS 100C • Setup Guide (Continued) Mask Patterns and Sensor Coverage An included infrared mask may be needed to achieve the desired sensory coverage. Any area masked will block the PIR sensor from detecting motion in that area.
  • Page 5 Installation OCS 100C Parts Installation Method 1 Secure mounting post to the ceiling tile with Ceiling nut and washer. Washer Twist and lock threaded Mounting Cutting End mounting post into the Post cover plate. Drill into ceiling tile. Threaded Mounting Post...
  • Page 6 Le contrôleur et l’OCS 100C doivent partager une connexion de mise à la terre commune pour éviter les risques de boucles de terre et une différence dans le potentiel de terre. The OCS 100C requires 24 VDC to power. If the sensor is connected to a device that does not provide 24 VDC, use the included PC 1224 power module: Connect a 12 VDC power source to the 12 VDC input on the supplied PC 1224 power converter (see figure 6).
  • Page 7: Troubleshooting

    Troubleshooting Problem Possible Cause Test Solution Sensor remains ON. Constant noise. Reduce both green and red Move sensor to a less noisy knobs by 1/8 (15%) turn or area within the room. remove noise source. Sensor remains OFF Sensitivity is set too low. Increase both green and red Move the sensor.
  • Page 8 For information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Extron Safety and Regulatory Compliance Guide on the Extron website. www.extron.com © 2017-2019 Extron Electronics — All rights reserved. 68-3155-51 Rev. G All trademarks mentioned are the property of their respective owners. 01 19...