Occupancy Sensor OCS 100W • Setup Guide
The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a
dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to
detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves.
The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the
ambient room temperature.
The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy
output connections.

Front Panel Features

Ultrasonic
Sensors
Ultrasonic
Sensors
Figure 1.
OCS 100W Front Panel Features
Control
DIP Switches (A)
DIP Switches (A)
A
Blue Timer Test Button
Red Infrared Sensitivity Dial
Blue Timer Test Button
Red Infrared Sensitivity Dial
Figure 2.
OCS 100W Controls
DIP Switches (B) — (see
B
OPERATION
1
Timer Setting
(B1 and B2 switches
must be set together)
2
B
OPERATION
3
Timer adjust
4
Sensitivity adjust
*Default
The settings for DIP Switches B3 (timer adjust) and B4 (sensitivity adjust can be set to Automatic mode or Manual mode.
Automatic mode — The sensors automatically adjust for changes in usage and seasons, eliminating the need for
manual adjustments and improving system performance.
Manual mode — The user sets the parameters of the sensors using the DIP Switches B1 and B2 set together, and
the dials.
Green LED
(status indicator)
Infrared/Photocell
Green LED
Sensor and Lens
(status indicator)
Red LED
Infrared/Photocell
(status indicator)
Sensor and Lens
Removable Front Cover
Red LED
(status indicator)
Removable Front Cover
DIP Switches (B)
DIP Switches (B)
B
A
B
Notch
Blue Photocell Dial
Green Ultrasonic Range Dial
Notch
Blue Photocell Dial
Green Ultrasonic Range Dial
NOTE
on the next page)
8 minutes:
OFF*
OFF *
OFF
Automatic
Automatic
Ultrasonic Sensors — Detect movement in the room, based on
ultrasonic waves.
Green LED (status indicator) — Flashes when the ultrasonic
sensors detect occupancy.
Infrared/Photocell Sensor and Lens — Diffracts the incoming
light and directs the light to the infrared/photocell sensor.
Red LED (status indicator) — Flashes when the infrared sensor
detects occupancy.
Removable Front Cover — Conceals all controls and DIP
switches.
DIP Switches (A) —
A
OPERATION
1
Not used
2
Not used
3
LED indicators
4
Automatic adjust
reset
*Default
Settings
4 minutes:
15 minutes:
30 minutes:
OFF
ON
ON
ON
OFF
ON
ON
Manual*
Manual*
OFF
ON
Not used*
Not used
Not used*
Not used
LEDs enabled*
LEDs disabled
Toggle to reset (Default: OFF)
1

Advertisement

loading

Summary of Contents for Extron electronics OCS 100W

  • Page 1: Front Panel Features

    Occupancy Sensor OCS 100W • Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people.
  • Page 2 Occupancy Sensor OCS 100W • Setup Guide (Continued) Timer Setting (B1 and B2) (see figure 2 on the previous page) — The occupancy sensor has a built in timer feature. • When the sensor detects motion, it instantly triggers ON (high). Once occupancy is no longer detected, the timer begins.
  • Page 3: Sensor Coverage

    Sensor Placement and Installation Options When placing the sensor in a room, be sure the sensor is not aimed out through a door. The sensor can detect hallway traffic, causing false triggers. PIR sensors trigger in response to changes in the amount of IR arriving from any of their segments of view within a direct line of sight from the sensor.
  • Page 4: Installation

    Occupancy Sensor OCS 100W • Setup Guide (Continued) OCS 100W Parts 10' - 0" Mounting Height Mounting Bracket 20' - 0" Minor Motion Coverage Pull Wiring Harness 40' - 0" Major Coverage Sensory Coverage Bracket Cover Mounting Bolt, US Minor Motion IR Minor Motion Washer and Nut.
  • Page 5 21 VDC in the OCS 100W Occupancy ON (High) state and 0 VDC in Sensor the OFF (Low) state. Figure 7. OCS 100W Wiring Diagram Relay Contacts Blue/White Common Black/White Normally closed when unoccupied NOTE: Relay contacts could be used to trigger third party devices, such as HVAC, based on occupancy.
  • Page 6: Troubleshooting

    • La source d’alimentation ne devra pas être fixée de façon permanente à la structure de bâtiment ou à d’autres structures similaires. © 2017-2018 Extron Electronics — All rights reserved. www.extron.com 68-3155-50 Rev. E All trademarks mentioned are the property of their respective owners.