Table 7. "C" values used to determine rupture disc vent line sizes – CVHE, CVHF and CVHG
Evaporator
Condenser
Size
Size
(EVSZ)
(CDSZ)
(3)
(4)
032S
032S
032S
032L
032L
032L
050S
050S
050S
050L
050L
050L
080S
080S
080S
080L
080L
080L
142E
142L
142M
142L
142L
142L
210L
210L
250E
250L
Notes:
1. To determine the total "C" value for a specific unit, add the appropriate ""C" values for the evaporator, standard condenser and economizer. If the unit is equipped
with any options (e.g., heat recovery, free cooling or an auxiliary condenser, add the applicable "C" values to this total. With this new sum, refer to Figure 13 to
determine the vent line pipe diameter.
2. If piping multiple rupture discs (multiple units) to a common vent line, first determine the total "C" value for each unit, and then; add all "C" values together and
apply the result to the "vent pipe sizing chart" in Figure 13.