3.5.1 Location drawing of installation foundation of the unit: (unit:
Aqua tempo power series tropical air-cooled scroll chiller 50Hz
mm)
225
Drainage channel
3.5.1 Location drawing of installation foundation of the unit: (unit:
mm)
230
Drainage channel
350
1551
Drainage
channel
Hole for anchor bolt
Schematic diagram of installation dimension of the unit

1.4 Installation of damping devices

Damping devices must be provided between the unit and its foundation.
By means of the Φ15mm diameter installation holes on the steel frame of the unit base, the unit can be
fastened on the foundation through the spring damper. See upper pictures (Schematic diagram of installation
dimension of the unit) for details about center distance of the installation holes. The damper does not go with
the unit, and the user can select the damper according to the relevant requirements. When the unit is installed
on the high roof or the area sensitive to vibration, please consult the relevant persons before selecting the
damper
164
1550
Anchor bolt
MGBT- F120W/RN1
2388
Anchor bolt
MGBT- F180W/RN1
1551
MGBT- F250W/RN1
Drainage channel
Drainage channel
Drainage channel
Concrete
MCAC-ATSM-2014-09
Concrete
Cement mortar
Concrete
Cement mortar
Cement mortar