Pressure Jet Oil Burner Installation / Electrical Supply - Wolf ComfortLine Series Installation And Maintenance Instructions Manual

Steel boilers up to 63 kw
Table of Contents

Advertisement

Pressure jet oil burner installation
The Unit pressure jet oil burner installation
instructions are included in the burner
packaging.
Only use bolts when securing the
burner to the boiler flange, whose
thread penetrates the boiler flange
by a maximum of 15 mm. Only use
pressure jet gas burners compliant
with EC Directive 90/396/EEC.
Electrical supply
Do not route sensor leads with
Note
230 V mains cables.
Connect the heating circuit pump(s) and the
DHW cylinder loading pump(s) on-site via
contactor, if:
• The burner and pump draw more than 2 A
each.
• The total control unit power consumption is
exceeded.
Observe the control unit installation and
operating instructions.

Pressure jet oil burner installation / Electrical supply

Burner flange holes
Boiler flange
Burner plug wiring diagram
Cable grommets
Electrical supply
2 5