The angle-type safety valve and the thermostat are set to the specified values by the manufacturer. Should
any modification be required, please follow the steps indicated below.
1
2
Fig. 11:
Angle-type safety valve
1 Cover nut
3 Adjusting screw
7.4.1 Pressure Setting on the Angle-type Safety Valve
PLEASE NOTE
A small amount of oil may leak from the valve.
The unit is switched off.
1)
Loosen cover nut using a metric AF36 wrench and dismount. Use second wrench of the same size at
point 4 in Fig. 10 for holding the valve in place.
2)
Loosen counter nut by turning it anticlockwise (use a AF36 wrench).
3)
Set adjusting screw to the pressure value required:
Screwing in will increase the pressure setpoint.
Screwing out will decrease the pressure setpoint.
4)
Tighten counter nut by turning it clockwise.
5)
Re-install cover nut and tighten.
Pressure setting is accomplished.
6)
Operate unit and check pressure.
If the intended pressure value is not yet reached, repeat the whole procedure.