Product Description

Specifications

4.4
Specifications
Dimensions and weight
Length:
Width:
Height:
Weight:
Coolant capacity:
Table 4:
Dimensions and weight
Performance data
Cooling capacity:
Pump capacity:
Mains voltage:
Power input:
Table 5:
Performance data
Environmental conditions
Operating temperature:
Storage temperature:
Relative humidity:
Table 6:
Environmental conditions
Settings
Flow control device
Thermostat
Maximum pressure
Table 7:
Settings
Laird Technologies GmbH
16
Operation Manual (Translation)
650 mm
350 mm
750 mm
49.6 kg (empty)
23 liters (Shell Diala S3-ZXIG)
4500 Watts at 22.8 K difference between the
oil outlet temperature and the ambient air
temperature
> 22 lpm at 3.5 bar
230 VAC  10% 50/60 Hz
785 Watts (P
; 230 V; 50 Hz)
max
1058 Watts (P
; 230 V; 60 Hz)
max
-10°C ... +40°C
-25°C ... +70°C
20% ... 90%
14.0 ± 0.3 lpm
55 ± 3 °C
9.0 +0.5/-0.2 bar