 No unauthorized changes on the unit are allowed. All intended changes must be authorized by the
manufacturer.

3.3.3 Environmental Issues

Environmentally concious and anticipatory behaviour of staff avoids environmentally hazardous impacts.
The following principles apply for environmentally conscious behaviour:
 Environmentally hazardous substances must not get into the soil or into the drains. They should be
kept in appropriate containers.
 Environmentally hazardous substances must be brought to utilization or disposal according to regional
regulations.
When dealing with working fluids always keep aware of the safety data sheet of the corresponding
manufacturer.

3.3.4 Protective Clothing

When doing a job that leads to contact of the skin with the coolant (e.g. filling-up of the coolant container):
3.4

Safety Equipment

PLEASE NOTE
The safety equipment listed below must be integrated in the local control environment by the customer,
unless otherwise noted. These tasks must be carried out solely by trained experts. All information required
can be taken from the wiring diagram shown in the addendum.
Safety equipment must not be modified, removed or taken out of operation. All parts of the safety equipment
must be accessible at all times.

3.4.1 Safety and Signalling Equipment included in the Unit

The unit is equipped with safety equipment at critical spots:
 The filling level of the coolant container is indicated in an inspection glass.
 The circulated oil amount is controlled by a flow control device (flow switch) that must be integrated in
the potential-free safety circuit of the device that is to be cooled.
 The oil temperature is controlled by a thermostat. When the oil temperature exceeds the maximum
setpoint this is indicated by the potential-free safety circuit.
 The maximum pump pressure is limited by an angle-type safety valve that bypasses the oil stream
when the pressure pre-set is exceeded.
Laird Technologies GmbH
Operation Manual (Translation)
Wear safety gloves made of PVC, neoprene or nitrile rubber
Date: 06-Jul-2015
Version: 2.0
Safety Regulations
Safety Equipment
Oil-Air Cooling Unit OL 4503
1264.00
11