Description
No
Name
1
Leaving Water Pipe
2
Entering Water Pipe
3
Refrigerant Pipe
4
Refrigerant Pipe
5
Water Pump
6
Safety Valve
7
Control Box
8
Thermal switch
9
Flow Switch
10
Plate Heat Exchanger
11
Pressure Gage
12
Expansion Tank
13
Air Vent
14
Electric Heater
15
Strainer
16
Shut-off valve
Male PT 1 inch
Male PT 1 inch
Ø9.52mm
Ø15.88mm
Max Head 9.5 / 7 / 6 m
Open at water pressure 3 bar
PCB and terminal blocks
Cut-off power input to electric heater at 90 °C
(manual return at 55C)
Minimum operation range at 15 LPM.
Heat exchange between refrigerant and water
Indicates circulating water pressure
Absorbing Volume change of heated water
Air purging when Charging water
Please refer to the below Page
'Model name and related information'
Filtering and stacking particles inside circulating water
To drain or to block water when pipe connecting
GENERAL INFORMATION
Remark