INSTALLER SETTING
104
NOTE
!
• Heater on temperature
Using Half capacity of electric heater : when DIP Switch No. 6 and 7 is set as 'OFF-ON' :
- Example : If Heater on temperature is set as '-1' and DIP switch No 6. and 7 is set as
'OFF-ON', then half capacity of electric heater will start operation when outdoor air
temperature is below -1 °C and current leaving water temperature or room air temperature
is much belower than target leaving water temperature or target room air temperature.
Using Full capacity of electric heater : when DIP Switch No. 6 and 7 is set as 'OFF-OFF' :
- Example : If Heater on temperature is set as '-1' and DIP switch No 6. and 7 is set as
'OFF-OFF', then full capacity of electric heater will start operation when outdoor air
temperature is below -1 °C and current leaving water temperature or room air temperature
is much belower than target leaving water temperature or target room air temperature.