2.3
Wiring
2.3.1
Terminal connection diagram
Sink logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
24V external power supply
24V power supply
Common terminal
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
Node address setting
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+.
Earth
(Ground)
Jumper
P1
MC
R/L1
S/L2
T/L3
Earth
(Ground)
+24
SD
Shorting
wire
S1
S2
PC
FL remote
communication
connector
X1
X10
Brake unit
(Option)
*1
R
*3
PR N/-
*2
P/+
V
W
Main circuit
Control circuit
Y0
SE
24V
D1 D2
D3 D4
Wiring
*2 A brake transistor is not built-in to the 0.1K
and 0.2K.
*3 Brake resistor (FR-ABR, MRS, MYS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor cannot be connected
to the 0.1K and 0.2K.)
Motor
IM
Earth (Ground)
Open collector output
Open collector output Y0
(Safety monitor output 2)
Open collector output common
Sink/source common
LED (operation status display)
D1: Communication setting status LED (CHG)
D2: Device status LED (DEV)
D3: Reception/transmission LED (TX/RX)
D4: Remote status LED (RMT)
5