2.3.3
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
Three-phase 200V class
FR-E720-0.1KNF to 0.75KNF
N/-
R/L1 S/L2 T/L3
Power supply
FR-E720-5.5KNF, 7.5KNF
R/L1 S/L2 T/L3
Power supply
Three-phase 400V class
FR-E740-0.4KNF to 3.7KNF
Jumper
N/- P/+
R/L1 S/L2 T/L3
PR
Power supply
FR-E740-11KNF, 15KNF
N/-
P/+ PR R/L1 S/L2 T/L3
Jumper
Power supply
NOTE
Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the inverter. Doing so will damage the inverter.
Connect the motor to U, V, W. Turning ON the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
Jumper
P/+
PR
IM
Motor
N/-
P/+ PR
Jumper
IM
Motor
IM
Motor
IM
Motor
FR-E720-1.5KNF to 3.7KNF
Jumper
N/- P/+
R/L1 S/L2 T/L3
PR
Power supply
FR-E720-11KNF, 15KNF
R/L1 S/L2 T/L3
N/-
Power supply
FR-E740-5.5KNF, 7.5KNF
Jumper
R/L1 S/L2 T/L3
N/-
P/+ PR
Power supply
Wiring
IM
Motor
P/+
PR
Jumper
IM
Motor
IM
Motor
7