18
UniGear ZS3.2
• Take care that the catch pins 51.1 on the inter-
lock yoke 51 are engaged with the guiding
rails 51.3 in the switchgear when moving-in
with-draw able part into the panel
4.4 Delivery and intermediate storage
The responsibilities of the consignee when
the switchgear arrives at site include, but are
not limited to, the following:
• Checking the consignment for completeness
and freedom from damage (e.g. also for
moistu-re and its detrimental effects). In cases
of doubt, the packaging must be opened and
then pro-perly resealed, fitting new drying
agent bags, when in termediate storage is
necessary
• Precisely documenting any short quantities,
de-fects or transport damage on the
consignment note and notifying the shipper
or carrier imme-diately and reporting these
to the relevant authorities within two weeks
• Always take photographs to document any
mayor damage
Optimum intermediate storage – as far as this
would be necessary at all – without detrimental
consequences depends on compliance with a
number of minimum conditions for the
switchgear panels and assembly materials.
Switchgear panels with simple packaging or
no packaging
• A dry and well-ventilated storeroom,
atmosphere in accordance with IEC 62271-200
I N S T R U C T I O N M A N U A L
• Room temperature which does not fall below
-15°C
• No other detrimental environmental influences
• Store switchgear panels standing upright
• Do not stack switchgear panels
• Do not remove or damage the packaging
• Loosely cover unpackaged switchgear panels
with plastic film to prevent dirt ingress.
Sufficient air circulation must be maintained
to prevent corrosion
• Carry out regular checks for any condensation
until erectionstarts
Switchgear panels with seaworthy or similar
pak-kaging and internal protective film
• Store the transport units in a dry place,
protected from the weather and from damage
• Check the packaging for undamaged condition
• Check the indicator for correct function of
the drying agent on arrival of the consignment
and at appropriate intervals, see also the
details in section 4.2
• When the maximum storage life after the date
of packaging is exceeded, the protective
function of the packaging including its anti-
corrosion effects will cease to be effective
sooner or later, depending on local conditions.
If intermediate storage has to be prolonged,
suitable action must be taken
Note:
Do not walk on the roof of the panels (rupture
points in pressure relief devices)!

Advertisement