connector of the mast butt adaptor. All conventional downconductors should be lugged and
fixed to the terminal per Figure 10
For structures made of combustible materials, downconductors must be separated from
the structure by a distance of at least 0.1 m and they must have a cross-sectional area of
100 mm
2
Installation on structures:
Minimum of two downconductors are required, preferably on opposite sides of the
structure
If natural components of the structure are used, electrical continuity to ground must be
checked
For installations where multiple Guardian Plus terminals are installed, the requirement
for two downconductors per terminal is waived
Standalone / isolated / freestanding mast installation:
Only one downconductor is required
Natural components, e.g., steel mast, may be used if it complies with the requirements
for downconductors (in general, a minimum cross-sectional area of 50 mm
Routing and installation:
Install externally wherever possible. Internal installation requires routing inside a non-
flammable insulating pipe
Keep the path as direct and straight as possible
Avoid sharp bends. Bend radius must not be smaller than 20 cm
Avoid routing along or across electrical conduits
Use three fasteners per metre
Protect against the risk of mechanical impact damage with guard tubes up to a height
of at least 2 m above the ground level
Natural components:
External interconnected steel frames (metal structures) may be used in place of ded-
icated downconductors if it is shown that the electrical continuity / resistance is ≤ 0.1
Internal metallic structures, concrete reinforcements, metal structures inside
walls, metal sheets and pipes at least 2 mm thick may be used to supplement
dedicated downconductors(s)
20
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
)
2
W
www.lpi.com.au