Lightning Protection International GUARDIAN PLUS Installation Manual page 20

Table of Contents

Advertisement

Minimise strain on the HVSC Plus downconductor
The HVSC Plus downconductor may be installed internally or externally on the structure
The HVSC Plus downconductor should be installed as close (flush) as possible to the
structure
Minimise the number of bends and use the most direct route to ground
Re-entrant loops ("doubling back") of the HVSC Plus downconductor MUST be avoided
Ensure minimum bend radius is not surpassed, i.e., smallest bend radius allowed is 430 mm
(20")
Parallel routing with other services should be avoided. If unavoidable, the minimum
separation distance is 2 metres (Figure 9)
If the HVSC Plus downconductor has to cross other services, ensure it crosses at right
angles. Use a conduit that extends at least 1 m beyond either side of the existing service
INCORRECT
CORRECT
Figure 9.
18
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
Radius < 430 mm
Radius
> 430 mm
< 2 m
2 m
www.lpi.com.au