from S7 mask, displayed only for unit with return fans, the return air flow can be adjusted: press
the setpoint value with arrow keys and press
The real air flow can be read from next mask S8.

2.5 Clock menu and time slots setting

select "Clock" menu
Current time and date can be set from this mask, while the day is automatically updated.
to enable and set time slots, input the Clock menu password and press the key
password is 0001.
from this mask, the daily time slots can be enabled (second line) and switch off the unit outside the time slots
(fourth line).
set start and end time of the daily time slot.
set the summer (cooling) indoor temperature setpoint inside the time slot (internal set, third line) and outside
the time slot (external set, fourth line).
set the winter (heating) indoor temperature setpoint inside the time slot (internal set, third line) and outside the
time slot (external set, fourth line).
Original instructions
Installation manual
8
again to confirm the new value.
.
key, adjust
; the factory Clock menu
We reserve the right to make changes without any prior notice.
UATYQ*Y1
Packaged Rooftop
4P522681-1A