Download Print this page

Honeywell V5832B Product Data page 2

Small linear valves pn16

Advertisement

V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
TWO-WAY VALVES
DN
k
order no.
VS
25
4.0
V5832B2075
25
6.3
V5832B2083
25
10.0
V5832B2091
32
16.0
V5832B2109
40
25.0
V5832B2117
THREE-WAY VALVES
DN
k
order no.
VS
25
4.0
V5833A2076
25
6.3
V5833A2084
25
10.0
V5833A2092
32
16.0
V5833A2100
40
25.0
V5833A2118
OPERATION
A built-in return spring produces a closing force.
The valves are supplied with an adjustment cap for manual
operation and to protect the stem. This allows the stem set up
for filling or initial heating/cooling during the building
construction phase without the use of a controller or actuator.
The small electric valve actuators provide automatic control
during the opening and closing movement of the valve stem.
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the
p-values exceed 60 kPa, attention should be paid to the
development of noise.
Two-Way Valves
Direction of flow always from port A to port B
Port B: Outlet
inlet
+
-
outlet
Fig. 1. Two-way valve operation
EN0B-0408GE51 R0612
close-off pressure (= max. operating
pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028)
1600
1600
1600
1200
1000
close-off pressure (= max. operating
pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028)
600
600
600
300
--
inlet
+
-
outlet
close-off pressure (= max. operating
pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
close-off pressure (= max. operating
pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
Three-Way Valves
These valves are preferably used as mixing valves, this
means:
Port AB:
Total flow outlet
Port A:
Controlled flow inlet
Port B:
Bypass inlet
inlet
AB
A
B
Fig. 2. Three-way valve operation
2
1600
1600
1600
1200
1000
1600
1600
1600
1200
1000
inlet
+
-
AB
A
B
+
-

Advertisement

loading

This manual is also suitable for:

V5833a