Note This signal word indicates important information (e.g. material damage), but does not indicate hazards. Info Information marked with this symbol helps you to carry out your tasks quickly and safely. desiccant dehumidifier TTR 800 / TTR 1400...
• relative humidity: max. 95 % RH non-condensing • Insert the mains plug (if any) into a properly secured mains After consultation with Trotec other operating conditions are power socket. possible with respectively modified versions. • Observe the device's power input, cable length and intended use when selecting extensions to the power cable.
Page 4
The device is not a toy and does not belong in the hands of children. Warning Risk of suffocation! Do not leave the packaging lying around. Children may use it as a dangerous toy. desiccant dehumidifier TTR 800 / TTR 1400...
In doing so, the contained moisture is withdrawn by the sorbent (silica gel) and retained (desiccation). Due to physical processes the temperature of the dry air (6) increases. Later the dried air flows towards the dry air outlet. desiccant dehumidifier TTR 800 / TTR 1400...
Page 6
Purging sector according to the specifications. Hence, additional throttle valves in the air lines are rendered redundant. Process air inlet Regeneration air inlet Dry air outlet Heater battery Humid air outlet (regeneration air) desiccant dehumidifier TTR 800 / TTR 1400...
Page 7
If a safety component is tripped, the device will be switched off (STOP), but the overrun will remain active. Wait until the entire rundown period has lapsed before accessing internal parts of the device. desiccant dehumidifier TTR 800 / TTR 1400...
Page 8
Ventilation mode for outdoor installation • The air transport line for the dry air outlet (11) is led into the room to be dehumidified in order to feed dry air into ΔP excess pressure desiccant dehumidifier TTR 800 / TTR 1400...
Page 9
Regeneration air inlet with connection for an air Regeneration air volume /h] / [Pa] transport line Weight [kg] Control box ventilation system incl. air filter(s) – Version Cable inlet for control lines Serial number – desiccant dehumidifier TTR 800 / TTR 1400...
Prior to installation and switching the device on, check whether all air filters are inserted. Information regarding the air filter installation and filter change can be found in the Maintenance chapter. desiccant dehumidifier TTR 800 / TTR 1400...
3. Loosen the screws (35) of the electrical control box cover. 4. Remove the electrical control box cover either by pulling it forwards or by lifting it. Designation Process air inlet Regeneration air inlet Humid air outlet (regeneration air) Dry air outlet desiccant dehumidifier TTR 800 / TTR 1400...
Page 12
1. Set the main switch to 0. 2. Loosen the screws and open the cover. ð The cover can only be opened if the main switch is set precisely to the 0 position! desiccant dehumidifier TTR 800 / TTR 1400...
Page 13
3. FILTER / WARNING These remote signalling contacts correlate with the lamps on the control panel (see description in the Operation chapter). For the correct assignment observe the wiring diagrams in the technical annex. desiccant dehumidifier TTR 800 / TTR 1400...
– target value fan speed regeneration air (Reg.) for adjusting the air volume via the fan speed. For adjustment work, measurements or the like, which have to be carried out during operation, one must on principle switch over to manual operation (ON-SITE)! desiccant dehumidifier TTR 800 / TTR 1400...
- motor fault of the fans regeneration air or process air contact has been activated, the BETRIEB / OPERATION - possibly collective fault messages of additional options lamp (39) will be illuminated – the device starts up. (see Technical annex) desiccant dehumidifier TTR 800 / TTR 1400...
• Have the device checked once a year by an electrically skilled person at any rate. 3. Then press the STÖRUNG / FAULT – RESET button (38) to acknowledge the STB faults or the ΔP fault message. desiccant dehumidifier TTR 800 / TTR 1400...
Page 17
• Check drive motor for proper functioning, have it replaced if necessary. • Check toothed belt pulley for tight fit, fasten it if necessary. • incorrect rotor rotation direction • Correct rotational direction. desiccant dehumidifier TTR 800 / TTR 1400...
Page 18
If the fault cannot be rectified despite following the checklist above, please contact one of our subsidiaries or our headquarters. desiccant dehumidifier TTR 800 / TTR 1400...
Dirty filters impair the performance ability of the dehumidifier. A filter change is required at the latest when the filter change indicator FILTER on the control panel lights up. desiccant dehumidifier TTR 800 / TTR 1400...
Page 20
1. To do so, open the filter flap at the electrical control box. 2. If it is dirty, replace the filter. Then close the flap again until it snaps into place. desiccant dehumidifier TTR 800 / TTR 1400...
Page 21
Do not use a cleaning agents containing solvents to avoid damage to the surfaces and operating elements of the devices. Clean the surfaces and operating elements of the devices with a damp cloth and solvent-free cleaning agents only. desiccant dehumidifier TTR 800 / TTR 1400...
Should you be unable to dispose of the device properly, please 4. Dispose of these supplies separately according to the contact the manufacturer and instruct him to carry out the applicable regulations. disposal on your behalf. desiccant dehumidifier TTR 800 / TTR 1400...
The Millenium control module is located behind the left section air volume. of the front cover inside the electrical control box. To be able to read the control module's display, first open the front cover of the device (see instructions): desiccant dehumidifier TTR 800 / TTR 1400...
Page 25
1Ext/2Int/3P Selection target value external = 1, internal = 2, control value external = 3 ACT.Moist Actual value humidity in [°Cdp] SetP.Int. Target value humidity in [°Cdp], can be modified SetP.Ext. Target value external humidity in [°Cdp], display only desiccant dehumidifier TTR 800 / TTR 1400...
Page 26
LOW=1: low speed 10. Control valve regeneration heating screen (optional) 1Ext2Int3Pas Selection target value external = 1, internal = 2, control value external = 3 Set.RegValve External signal Out RegValve Output O6 PWM signal Control value for control valve regeneration heating desiccant dehumidifier TTR 800 / TTR 1400...
Page 27
Basic settings operation The basic settings are made in the factory. Signal conversions and the corresponding scales must be coordinated with Trotec Warning of electrical voltage prior to delivery or can be adjusted (optionally) during start-up Work on the electrical components must only be by Trotec service personnel.
Page 28
Error and fault messages can be reset by pressing the reset button. 6. Set a jumper from X6.40 to X6.41. The modifications are completed. desiccant dehumidifier TTR 800 / TTR 1400...
Page 29
If an additional heating is used, the STB • Check setting at STB, adjust. is prompted, too. • Check regeneration air volume. If the fault cannot be rectified, please contact one of our subsidiaries or our headquarters. desiccant dehumidifier TTR 800 / TTR 1400...
Page 30
5. Press the "P" button. The indication flashes. its maximum speed. 6. Use the buttons ▲ / ▼ to reduce or increase the set value as desired. 7. Finally press the "P" button to save the settings for the new target value. desiccant dehumidifier TTR 800 / TTR 1400...
Page 31
2. Unscrew the protective cap of the STB reset device "7B1". 3. The STB can now be reset with a pen or screwdriver. 4. Afterwards, screw the protective cap back on. desiccant dehumidifier TTR 800 / TTR 1400...
Page 32
• exhaust pipe arc for humid air • control panel protection Note Suitable on-site roofing or similar shall be provided in order to protect the device from a high solar irradiation (overheating) and snow loads (penetration of snowmelt). desiccant dehumidifier TTR 800 / TTR 1400...