Step 5: Flame Monitoring Control System - Eclipse RA Series Design Manual

Ratioair burners
Table of Contents

Advertisement

Step 4:
Ignition System
(Continued)
Step 5:
Flame Monitoring
Control System
Flame Rod
UV Scanner
Eclipse RatioAir v1 Design Guide No. 115, 11/12/2008
Ignition Gas Piping
RatioAirs are capable of ignition with either low fire or bypass start
gas.
Low Fire Start:
Main gas
shut-off
valve train
Bypass Start Gas (Optional):
Main gas
shut-off
valve train
NC
Optional fuel orifice meter recommended.
An optional fuel orifice meter connected in the start gas piping can
simplify start-up and adjustment. To start the burner at the lowest
possible gas input, select a fuel orifice meter for 5" to 10" w.c.
pressure drop when the gas flow is at the burner's rated low fire.
The flame monitoring control system consists of two main
components:
Flame Sensor
Flame Monitoring Control
Flame Sensor
Two types can be used on a RatioAir Burner:
Flame Rod
UV scanner
Flame rods are available on model RA0025, RA0040, RA0075
and RA0100 burners with alloy or SiC tubes. A flame rod can also
be used on RA0200 burners but with upright left hand piping or
inverted right hand piping configurations only. Further information
can be found in:
Info Guide 832
A UV scanner can be used on all RatioAir Burner sizes. Further
information can be found in:
Info Guide 852; 90° UV scanner
Info Guide 854; straight UV scanner
Instruction Manual 855; solid state UV/IR scanner
Info Guide 856; self-check UV scanner
NC