Power And Grounding Cables Installation Check; Table 17 Connection Relationship - Zte ZXSDR R8860 Installation Manual

Cdma remote radio unit
Hide thumbs Also See for ZXSDR R8860:
Table of Contents

Advertisement

Monitoring Cable
Context
Steps
The End A connector should be equipped with metal dust-proof
cover
The labels printing and pasting should satisfy the requirements
of Q/ZX04.113.4 Cable Designing Criteria – Label Designing
and Usage Requirements.
The following are the technical specification of monitoring cable:
The End A is a 37-pin female connector.
End B is an open end without any connector. The connector at
the End B should be prepared on-site according to the on-site
requirements.
Make sure that connector at the End A is properly welded.
The label attached at both ends should satisfy the requirements
of ZTE Cable Designing Criteria – Label Designing and Usage
Requirements.
Table 17
shows the connection relationship of End A.
T
17 C
ABLE
ONNECTION
End A (Pins)
15/16
17/18
19/20
21/22
23/24
25/26
Other Pins are free
Power and Grounding Cables
Installation Check
Ensure the power and grounding cables installation is done in ac-
cordance with the following checks:
1. The power and grounding cables are laid separately from other
cables. If the power and grounding cables are to be laid par-
allel with other cables, then at least a distance of 20 cm is
maintained between them.
2. The cable labels are intact on both sides of power and ground-
ing cables. The labels are attached at almost 2 cm from cable
copper lug.
3. Entire power and grounding cables are made from one material
with no connections in between.
4. A single grounding point on the grounding busbar just connects
to a piece of equipment.
5. Copper lugs on both ends of power and grounding cables are
soldered or pressed firmly.
Confidential and Proprietary Information of ZTE CORPORATION
Chapter 6 Hardware Installation Inspection
R
ELATIONSHIP
Color
White/blue
White/orange
White/green
White/brown
Red/blue
Red/orange
Other core wires are
free
Signal Definition
Dry contact 4 - / +
Dry contact 3 - / +
Dry contact 2 - / +
Dry contact 1 - / +
485 Rx - / +
485 Tx - / +
119

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents