Attach The Ground Cable - Dell S60 System Manual

Table of Contents

Advertisement

Attach the Ground Cable

The S60 system is shipped with two 10-32 screws to attach a ground cable to the system. The cable is not
included. To properly ground the system, Dell Networking recommends using a 6AWG two-hole lug, #10
hole size, 63" spacing (not included). The two-hole lug must be a UL recognized, crimp-type lug.
NOTE: Coat the two-hole lug with an anti-oxidant compound prior to crimping. Bring any un-plated mating
surfaces to a shiny finish and coat with an anti-oxidant prior to mating. Plated mating surfaces must be clean
and free from contamination.
NOTE: The rack installation "ears" are not suitable for grounding.
CAUTION: Grounding conductors must be made of copper. Do not use aluminum conductors.
To connect the ground cable to the system, follow these steps:
Step
Task
Take the two 10-32 screws from the package.
1
Cut the cable to the desired length. The cable length must facilitate the proper operation of the fault interrupt
2
circuits. Dell Networking recommends using the shortest cable route allowable.
Attach the two-hole lug to the system using the supplied 10-32 screws with captive internal tooth lock washers.
3
Torque the screws to 20 in-lbs.
Attach the other end of the ground cable to a suitable ground point. The rack installation "ears" are not a suitable
4
grounding point.
1
2
Install the S60 System
|
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Force10 s60 series

Table of Contents