Installation instructions
for your new
Before you begin – Read these instructions completely and carefully.
IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer – Be sure to leave these instructions with the Consumer.
Note to Consumer – Keep these instructions with your Owner's Manual for future reference.
TOOLS NEEDED
• 1/4" Nut driver
• Wire cutter (For direct connect applications only.)
• This kit is for use with 230/208 volt 5200, 5500, and
7500 Series GE Zoneline units only.
230/208 VOLT ELECTRICAL SUPPLY
A power supply kit must be used to supply power to the
Zoneline unit. The appropriate kit is determined by the
voltage, the means of electrical connection, and the
amperage of the branch circuit. See the POWER
CONNECTION CHART to confirm the appropriate kit.
Power supply kit
All wiring, including installation of the receptacle,
must be in accordance with the NEC and local codes,
ordinances, and regulations.
Tandem
Perpendicular
15 Amp
20 Amp
230/208 volt receptacle configuration
POWER CONNECTION CHART
GE 230/208 Volt
Power Supply Kit
Configuration
RAK3152
RAK3202
Perpendicular
RAK3302
Large Tandem
• Phillips screwdriver
Large Tandem
30 Amp
Wall Plug
Circuit Protective Device
Tandem
15-Amp Time-Delay Fuse or Breaker
20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
RAK3152, RAK3202,
RAK3302
Power Supply Kit for Cord
or Direct Connection
CAUTION:
Disconnect the electrical power
supply before wiring connections.
IMPORTANT NOTES
• This unit must be properly grounded.
• The electrical rating marked on the previously installed
Zoneline and power supply kit must be the same as
the supply branch circuit.
• Aluminum building wiring may present special
problems—consult a qualified electrician.
• All wiring, including installation of the receptacle,
must be in accordance with the NEC and local codes,
ordinances, and regulations.
• Use ONLY the wiring size recommended for single
outlet branch circuit.
• Proper current protection is the responsibility of
the owner.
Recommended branch circuit wire sizes*
Nameplate
maximum circuit
breaker size
15A
20A
30A
AWG – American Wire Gauge
*
Single circuit breaker from main box
** Based on copper wire, single-insulated conductor at 60°C
NOTE: Use copper conductors only.
Heater Wattage
@ 230/208 Volts
2.55/2.09 KW
3.45/2.82 KW
5.00/4.10 KW
AWG wire
size**
14
12
10