6 Configuration

NOTICE
Output signals. The outdoor unit is provided with a
terminal (X3M) that can output 4 different signals. The
signal is 220~240 V AC. The maximum load for all signals
is 0.5  A. The unit outputs a signal in the following
situations:
▪ C/C1: caution signal – connection recommended –
when an error occurs that does not stop unit operation.
▪ C/W1: warning signal – connection recommended –
when an error occurs that causes unit operation to
stop.
▪ R/P2: run signal – connection optional – when the
compressor is running.
▪ P1/P2: operation signal – connection mandatory –
when the indoor unit solenoid valve is being controlled.
6 Connect the power supply as follows:
3N~ 50 Hz
380-415 V
L1 L2 L3
a
b
c
L1 L2 L3
N
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable
NOTICE
Keep cables away from the left maintenance stop valve
and piping. The valve and piping can get very hot and
damage the cables.
7 Fix the cables with cable ties.
X1M
X3M
a
b
a
Power supply (including earth)
b
Output signals
c
Remote operation switch, low-noise switch, transmission
Installation and operation manual
22
X1M
X2M
c
8 Route the wiring through the frame and connect it to it.
Routing through
the frame
b
a
a Power supply cable and output signal
cables
b Remote operation switch cable, low-
noise switch cable, and transmission cable
Connecting to the
When cables are routed from the unit, a
frame
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
9 Reattach the service cover.
10 Connect an earth leakage circuit breaker and fuse to the power
supply line.
6
Configuration
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
6.1

Making field settings

6.1.1

About making field settings

INFORMATION
The LEDs and buttons are located in the outdoor module
(not in the hydro module).
To configure the condensing unit, you must give input to the outdoor
unit's main PCB (A1P). This involves the following field setting
components:
▪ Push buttons to give input to the PCB
2
1
b
a
A B
a b c
d
e
LRMEQ+LRLEQ3+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lrleq4by1

Table of Contents