Refrigerant Piping Length And Height Difference; To Select The Expansion Valve; Preparing Electrical Wiring; Safety Device Requirements - Daikin LRLEQ3BY1 Installation And Operation Manual

Air-cooled refrigeration condensing unit
Hide thumbs Also See for LRLEQ3BY1:
Table of Contents

Advertisement

Description
(b)
Refnet joint
(a)
Do NOT connect 2 or more headers in series. For the gas
side choose the refnet header so that the diameter of the
header is equal to the main piping diameter or equal to one
size-up of the main piping diameter.
(b)
Choose the refnet joint so that the incoming and outgoing
piping diameters match with one of the available diameters
of the refnet joint. For more information, see
"4.2.3 Refrigerant piping material" on page 10
"4.2.4 To select the piping size" on
INFORMATION
Maximum 8 branches can be connected to a header.
4.2.6
Refrigerant piping length and height
difference
The piping lengths and height differences must comply with the
following requirements.
(see example in
"4.2.4 To select the piping size" on
Requirement
Maximum actual piping length
▪ Example: a+b+c+d2≤Limit
Maximum total piping length
▪ Example: a+b+c+d1+d2+e+f≤Limit
Maximum length first branch kit-indoor
unit
▪ Example: b+c+d2≤Limit
Maximum height
Outdoor higher than
difference outdoor-
indoor
indoor
▪ Example: H≤Limit
Outdoor lower than
indoor
Maximum height difference indoor-indoor
4.2.7

To select the expansion valve

This unit has a larger subcooling ratio for the liquid refrigerant
compared to units without a subcooling mechanism, as the liquid
refrigerant is being cooled by a double tube heat exchanger
(subcooling ratio = condensing temperature–liquid refrigerant
temperature at outdoor unit outlet).
When selecting an expansion valve for the load according to the
technical information of the expansion valve manufacturer, take into
account the subcooling ratio (K) for the liquid refrigerant in the table
below.
For LRMEQ3+4
Subcooling ratio (K)
Te –20°C
–15°C
–10°C
Tc
20°C
10
9
25°C
11
10
30°C
12
11
35°C
13
12
40°C
14
13
45°C
15
14
50°C
16
15
55°C
16
15
LRMEQ+LRLEQ3+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09
Model name
KHRQ22M20T
KHRQ22M29T9
and
page 10.
page 10)
Limit
50 m
80 m
30 m
20 m
10 m
5 m
–5°C
0°C
5°C
8
7
6
5
9
8
7
6
10
9
8
7
11
10
9
8
12
11
10
9
13
12
11
10
14
13
12
11
14
13
12
11
For LRLEQ3+4
Subcooling ratio (K)
Te –45°C
–40°C
–35°C
Tc
20°C
19
18
25°C
20
19
30°C
21
20
35°C
22
21
40°C
23
22
45°C
24
23
50°C
25
24
55°C
25
24
4.3

Preparing electrical wiring

4.3.1

Safety device requirements

Power supply
The power supply must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.
Model
Minimum
circuit
ampacity
LRMEQ3 +
6.5 A
LRLEQ3
LRMEQ4 +
9.1 A
LRLEQ4
Remote operation switch, low-noise switch and output signals
wiring
NOTICE
Remote operation switch. The unit is factory-equipped
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn outdoor
unit operation ON/OFF, a remote operation switch is
required. Use a voltage-free contact for microcurrent
(≤1  mA, 12  V  DC). Connect to X2M/C+D, and set to
"Remote ".
The operation switch is located in the switchbox (see illustration
below).
The operation switch can be set to the following three positions:
Operation switch setting Function
OFF
Unit operation turned OFF
ON
Unit operation turned ON
Remote
Unit controlled (ON/OFF) with remote
operation switch
4 Preparation
–30°C
–25°C
–20°C
17
16
15
14
18
17
16
15
19
18
17
16
20
19
18
17
21
20
19
18
22
21
20
19
23
22
21
20
23
22
21
20
Recommended
Power supply
fuses
16 A
3N~ 50 Hz
380-415 V
OFF
Installation and operation manual
11