Connecting The Electrical Wiring; Field Wiring: Overview - Daikin LRLEQ3BY1 Installation And Operation Manual

Air-cooled refrigeration condensing unit
Hide thumbs Also See for LRLEQ3BY1:
Table of Contents

Advertisement

5 Installation
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes CO
equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
5.7

Connecting the electrical wiring

5.7.1

Field wiring: Overview

Field wiring consists of the following:
A
X3M
C
C1
W1
e
f
g
X1M
L1
L2
L3
N
h
b
d
T1
Ry0
Ry 1
Ry 1
NC
T1
No
Ry 0
Ry 0
Ry 0
K1M
Ry 0
Ry 0
TeS1
Ry 0
b
K1M
A
Outdoor unit
B
Indoor unit
a
To outdoor unit
b
Earth leakage circuit breaker
c
High voltage wiring intake
d
Control board (field supply)
e
Caution signal
f
Warning signal
g
Run signal
h
Operation signal
i
Earth
j
Remote operation switch
k
OFF: normal mode
ON: low-noise mode
T1
Timer
RY0, RY1
Relay
H1P
Defrost indicator
K1M
Contactor defrost heater
E1H
Defrost heater
S1T
Inner temperature adjustment thermostat
S2T
Defrost completion thermostat
Y1S
Solenoid valve
Installation and operation manual
20
c
R
P1 P2
X2M
A
B
C
D
F1 F2
i
j
k
B
S1T
Y1S
S2T
E1H
K1M
H1P
B
S1T
Y1S
S2T
E1H
K1M
H1P
3D111889
3N~ 50 Hz
380-415 V
L1 L2 L3
a
2
b
c
L1 L2 L3
N
X1M
a
Earth leakage circuit breaker
b
Fuse
c
Power supply (including earth) (sheathed cable)
d
Low-noise switch
e
Remote operation switch
f
Transmission
g
Caution signal
h
Warning signal
i
Run signal
j
Operation signal
NOTICE
The operation output P1/P2 of the outdoor unit must be
connected to all solenoid valves that are installed upstream
of the expansion valves at the indoor unit. This connection
is required because the outdoor unit must be able to
control the solenoid valves during startup (to prevent liquid
refrigerant from entering the compressor) and oil return
operation.
NOTICE
Remote operation switch. The unit is factory-equipped
a
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn outdoor
unit operation ON/OFF, a remote operation switch is
required. Use a voltage-free contact for microcurrent
(≤1  mA, 12  V  DC). Connect to X2M/C+D, and set to
b
"Remote ".
NOTICE
Low-noise switch. If you want to remotely turn ON/OFF
low-noise operation (see setting [2‑18]), you must install a
low-noise
switch.
microcurrent (≤1 mA, 12 V DC). Connect to X2M/A+B.
b
NOTICE
Output signals. The outdoor unit is provided with a
terminal (X3M) that can output 4 different signals. The
signal is 220~240 V AC. The maximum load for all signals
is 0.5  A. The unit outputs a signal in the following
situations:
▪ C/C1: caution signal – connection recommended –
when an error occurs that does not stop unit operation.
▪ C/W1: warning signal – connection recommended –
when an error occurs that causes unit operation to
stop.
▪ R/P2: run signal – connection optional – when the
compressor is running.
▪ P1/P2: operation signal – connection mandatory –
when the indoor unit solenoid valve is being controlled.
X3M
C C1 W1 R P1 P2
A
B
C
D
g
h
i
j
d
e
Use
a
voltage-free
contact
LRMEQ+LRLEQ3+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09
X2M
F1 F2
f
for