Daikin LRLEQ3BY1 Installation And Operation Manual page 28

Air-cooled refrigeration condensing unit
Hide thumbs Also See for LRLEQ3BY1:
Table of Contents

Advertisement

8 Troubleshooting
Code
Description
Wet operation from refrigeration
suction pipe
Wet operation from injection pipe Suction superheat ≥5 K AND discharge
3‑sensor error
High pressure switch failure
Outdoor fan motor signal failure
Outdoor air thermistor failure
Discharge thermistor failure
Suction thermistor failure
Heat exchanger inlet thermistor
failure
Heat exchanger outlet thermistor
failure
High pressure sensor failure
Low pressure sensor failure
Inverter PCB malfunction
Radiation fin temperature rise
Inverter compressor
instantaneous overcurrent
Inverter compressor overcurrent
Defective inverter compressor
startup failure
Transmission error between
control PCB and inverter PCB
Inverter compressor power
voltage imbalance
Radiation fin thermistor
Reversed phase / Open phase
Inverter compressor abnormal
power voltage
Installation and operation manual
28
Criteria
Suction superheat <5 K AND discharge
superheat <15 K AND discharge temperature
<60°C, continuously for 10 minutes
In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours
superheat <15 K AND discharge temperature
<60°C, continuously for 90 minutes
In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours
When 3 or more sensors detect abnormality
No continuity of high pressure switch
Abnormal position of signal of 1 fan motor
Abnormal position of signal of 2 fan motors
Open circuit or shortcircuit
Open circuit or shortcircuit
Open circuit or shortcircuit
Open circuit or shortcircuit
Open circuit or shortcircuit
Open circuit or shortcircuit
Open circuit or shortcircuit
IGBT error
93°C
≥16.1 A
Transmission failure between main PCB and
inverter PCB
Radiation fin thermistor open circuit or short
circuit
Reversed phase or open phase
Times of
Output signal
retry
0
Caution
Excessive frost formation on indoor
side
Wrong selection of expansion valves
0
Warning
0
Caution
Defective expansion valve, suction pipe
thermistor, or subcool heat exchanger
outlet thermistor
Refrigerant overcharge
0
Warning
0
Warning
Faulty connection of sensor
Defective sensor or outdoor unit PCB
0
Warning
Faulty connection of switch
Defective swith or outdoor unit PCB
4
Caution
Abnormal fan motor signal (circuit
error)
4
Warning
Broken, short, or disconnected
connector of fan motor connection
cable
Defective inverter PCB
0
Caution
Faulty connection of sensor
Defective sensor
0
Warning
Faulty connection of sensor
Defective sensor
0
Caution
Faulty connection of sensor
Defective sensor
0
Warning
Faulty connection of sensor
Defective sensor
0
Warning
Faulty connection of sensor
Defective sensor
0
Caution
Faulty connection of sensor
Defective sensor
0
Warning
Faulty connection of sensor
Defective sensor
0
Warning
Defective inverter PCB
9
Warning
Fin temperature rise because of
inverter malfunction
Fin temperature rise because of short
circuit
Fin thermistor malfunction
9
Warning
9
Warning
4
Warning
No limit
Caution
Defective connection between main and
inverter PCB
9
Warning
Unbalanced power supply voltage
No limit
Caution
Defective radiation fin thermistor, inverter
PCB, inverter compressor, or fan motor
0
Warning
Faulty connection of phase order to power
supply terminal X1M
9
Warning
Insufficient power supply voltage
Cause
Solution
Adjust defrost cycle
Select the correct type of expansion
valve
Replace defective component
Adjust refrigerant charge
Connect the sensor properly
Replace defective component
Connect the switch properly
Replace defective component
Ensure correct connection
Replace the fan motor
Replace the inverter PCB
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Connect the sensor properly
Replace defective component
Check for external causes (e.g. EMI
noise), or replace the inverter PCB.
Remove any obstacles that block the
passage of air to the outdoor unit
Check connection on PCB
Replace defective component
Replace defective component
Check if power supply is within range
Replace defective component
Make sure the phase order to X1M is ok
Make sure there is sufficient power supply
voltage
LRMEQ+LRLEQ3+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09