Section 4 / Detector Pinout Data - Honeywell SS2 Series Installation Manual And Operating Manual

Multi-spectrum digital electro-optical fire detectors
Table of Contents

Advertisement

SECTION 4 / DETECTOR PINOUT DATA

TABLE 1: Stand-Alone Model SS2 Detector Connectors - Pinouts
HONEYWELL
J1: DETECTOR INPUT POWER
PIN
1 D.C. Return or Ground (-)
2 NOT USED (Do not connect anything to this Pin.)
3 NOT USED (Do not connect anything to this Pin.)
4 Power (+24 Volts D.C.)
J2: FAULT RELAY
(SS2-A, -AN, -AM, -AML, AH)
PIN
1 Fault Relay Common
2 Fault Relay Normally Closed
3 Fault Relay Common
4 Fault Relay Normally Open
J3: FIRE RELAY
PIN
1 Fire Relay Common
2 Fire Relay Normally Open
3 Fire Relay Common
4 Fire Relay Normally Closed
OPERATOR MANUAL // SECTION 4 / DETECTOR PINOUT DATA
J2: FIRE RELAY #2
(SS2-AMD, -AMDL, -AHD)
PIN
1 Fire Relay #2 Common
2 Fire Relay #2 Normally Open
3 Fire Relay #2 Common
4 Fire Relay #2 Normally Closed
18

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ss2-aSs2-anSs2-amSs2-ah