the Detector should be pointed to the fire threat area. When multiple
detectors are used to cover large areas, the Fields-of-View should overlap.
The Field-of-View is not limited to 120 degrees. Larger fires outside
Figure 1. Field of View, Horizontal and Vertical.
Maximum Sensitivity to 1 Sq. Ft. Gasoline Pan Fire

Testing

Special Conditions for Testing

The SS2 Detector should be tested immediately after installation, after
repair or maintenance involving wiring or module replacement, after
periodic maintenance, or after lens contamination has been identified.

Automatic Testing

The Model SS2 Detectors contain an internal source for self-testing. For
testing the Model SS2 Detectors end-to-end for both optical path and
window cleanliness, use a Honeywell Analytics Model FT-2045 Test Lamp.

Manual Testing

For manual testing the Detector may be exposed to an actual industry
standard open flame or to a Test Lamp simulating a fire. For Honeywell
Analytics model SS2 Multi-Spectrum Fire Detectors, it is mandatory to use
the handheld UV/IR Test Lamp, Model No FT-2045 or FT-2145.
NOTE: Other manufacturers UV/IR Test Lamps should not be
utilized to test Honeywell Analytics Detectors, and Honeywell
Analytics Model FT-2045 and FT-2145 Test Lamps should not be
utilized for testing other manufacturer's Detectors.