Daikin VRV III-S Technical Data Manual page 12

Intelligent manager manual
Hide thumbs Also See for VRV III-S:
Table of Contents

Advertisement

5
Functions
5 - 2 Detailed Explanation of Functions
5 - 2 - 2 Control, Operation, Settings
Control, Operation, Settings
Login settings
Individual control
Collective starting/stopping and settings for control group
Schedule control
Interlocking control
Emergency stop control for fires
Power failure and recovery processing control
Centralized control of air conditioners
(1) Login settings
Sets user operation authority to control the range of operation and view, consultation, read, read-only. When logging in, the users can operate the
intelligent Manager within their allocated authority.
30 users can be registered and passwords can be set individually.
When unmanned, this is set to a log-off status. Settings can also be set for the log-off status.
It is possible to limit personnel who may operate intelligent Manager to prevent mis-operation or unauthorized handling.
The following shows authorization levels that can be set.
Authorization
Running/Stopping/Setting
Schedule Registration
Interlock Control Registration
Emergency Stop Registration
Emergency Stop Canceling
Report Inspection
Report Registration
History Operation
System Settings
Subordinate Centralized Control Setting
User Registration
Maintenance Mode
(2) Individual Control
Allows manual, individual operation of starting and stopping of management items. Operations for starting and stopping, switching the operating mode,
changing the temperature settings, switching enable/disable of individual remote controllers and for resetting of the filter sign are possible when using
DIII-NET compatible air conditioners.
Items pressed later have priority with regard to management items defined by the schedule control and interlocking control.
(3) Collective starting/stopping and settings for control group
Registering a plurality of management items to a control group allows manual starting and stopping for all equipment. Operations for starting and
stopping, switching the operating mode, changing the temperature settings, switching enable/disable of individual remote controllers and for resetting
of the filter sign are possible when using DIII-NET air conditioners.
Items pressed later have priority with regard to management items defined by the schedule control and interlocking control.
Registers a maximum of 1024 management items in one group and a maximum of 200 groups.
Can perform run/stop/set operations
Can inspection, register and edit schedules
Can inspection, register and edit link control
Can inspection, register and edit emergency stop
Can cancel emergency stop
Can inspect reports (daily, monthly annual)
Can set reports (daily, monthly annual)
Can inspect and set history
Can set system
Can set centralized control
Can register users and set authority
Can set maintenance mode
• VRV Systems • Network Solution
When Authorized
When Not Authorized
Cannot perform run/stop/set
Can only inspect schedule
Can only inspect link operation
Can only inspect emergency stop
Cannot operate
Cannot inspect
Cannot operate
Can only inspect history
Cannot operate
Cannot operate
Cannot operate
Cannot operate