HotSwap MBP models:
Input
Output
Dimensions
(HxLxD)
Performances
Nominal voltage
Frequency
Input nominal current
Maximal power
Standards
Product
Marking
Environment
Temperature
Humidity
Altitude
86-58100-00 A03
MBP - 115, MBP - 120, MBP - 130
MBP - 115
MBP - 120
MBP - 130
MBP - 115
MBP - 120
MBP - 130
2.1 x 17.3 x 3.8 inches
MBP - 115
MBP - 120
MBP - 130
MBP - 115
MBP - 120
MBP - 130
MBP - 115
MBP - 120
MBP - 130
C UL US LISTED
Storage -25°C to 55°C (-77°F to 131°F), operation 0°C to 45°C (32°F to 113°F)
Storage 10% to 90%, operation 20% to 90%
Transportation up to 12000 m (39370 ft), operation up to 1500 m (4921 ft)

Technical Specifications

Technical Specifications
NEMA 5-15P 15A cord (3.3 ft length)
NEMA 5-20P 20A cord (3.3 ft length)
NEMA L5-30P 30A cord (3.3 ft length)
6 NEMA 5-15R 15A socket outlets
6 NEMA 5-20R 20A socket outlets
5 NEMA 5-20R 20A socket outlets
100/104/110/120/127
50/60 Hz
12 A
16 A
24 A
1440 VA
1920 VA
2880 VA
UL 1778