MCT-560
English
Wireless Temperature Detector
Detectores de Temperatura Supervisionado Sem Fios PowerCode
Português
Instruções de Instalação
Detector
Español
Instalación.
ENGLISH
1. General
The MCT-560 is a fully supervised wireless PowerCode detector used
with the PowerMax Pro (Ver. 5), PowerMax COMPLETE, and Amber
alarm systems. The detector alerts the alarm system control panel upon
detecting critical indoor or outdoor temperatures. The detector
generates an alarm message when its sensor detects that the
temperature has reached a certain temperature point. A restore
message is generated when it crosses back the threshold temperature
point. There are a total of four fixed temperature points and the user can
enable one or more temperature point. The MCT-560 can be used in
instances where temperature detection is critical.
Other examples of detector usage are as follows:
Activating and deactivating pipe heaters at locations where low
temperatures may causes the water in pipes to freeze.
Warn of possible electrical device malfunction due to high or low
temperature levels.
Alerting elderly people of a significant rise or drop in room temperature.
The MCT-560 detects both indoor and outdoor temperatures. The detector
monitors room temperature using an internal sensor. For outdoor or
refrigerator installations, a waterproof temperature probe (optional) is used.
When the probe is connected, the temperature measurement is
performed only by the probe sensor. When the probe is not
connected, the temperature measurement is performed only by the
detector's internal sensor.
Once the predefined temperature is reached, the detector wirelessly
updates the alarm system control panel which then sends a notification to
the central station or uses the PGM/X-10 controls to switch on a
connected appliance, for example, a heater or air conditioner.
Note: When using the temperature probe to monitor refrigerator
temperature, the temperature probe is installed inside the refrigerator, while
the detector is installed on the wall or ceiling. For outdoor installations, the
temperature probe is installed outdoors, while the detector is installed
indoors.
Upon alarm, a digital message is transmitted, composed of the unit ID
followed by message data.
Since messages transmitted by the MCT-560 might collide with
transmissions from other PowerCode detectors, a "smart" anti-
collision transmission sequence is used.
The MCT-560 tamper switch is activated when the MCT-560 is
removed form the mounting surface or when the MCT-560 securing
screw (see Fig. 4 point 1) is removed. A periodic supervision
message is transmitted automatically once every 15 or 60 minutes, or
according to local requirements.
An LED lights whenever alarm, alarm restore or tamper events are reported.
Operating power is obtained from an on-board 3 V Lithium battery. A
weak battery will result in a "low battery" message.
Features
The MCT-560 is compatible with supporting versions of PowerMax
Pro, PowerMax COMPLETE, and Amber.
Note: There is no backward compatibility with PowerMax and
Amber models produced before the year 2007.
Internal sensor
An external temperature probe (cat. no. 99-300890) enables
outdoor and refrigerator temperature sensing
Four selectable temperatures
Fully supervised PowerCode detector
Front and back tamper
Long battery life
Low battery supervision
Probe disconnected supervision
Alert transmission indication using an LED
D-300872
Installation Instructions
de
Temperatura
inalámbrico,
Fig. 1 – GB/US: MCT-560 with Temperature
instrucciones
de
Probe / PT: MCT-560 com Sonda de
Temperatura / SP: Sonda de Temperatura
2. Specifications
Frequency (MHz): 315, 433.92, 868.95, 869.2026 or other frequency
per local requirements.
Communication Protocol: PowerCode
Detector's ID Code: 24-bit digital word, over 16 million combinations,
pulse width modulation
Temperature Alarm or Tamper Message Repetition: Repetitive
transmission (once every 15 minutes) until the alarm is restored.
Supervision: Signaling at 60 min. (USA) or 15 min. (Europe) intervals.
RFI protection: >20 V/m 80 to 2000 MHz
Temperature measurement accuracy (internal sensor or optional
probe): ±1.5°C (±2.7°F)
Probe cable length: 3.5m
Power Source: 3V Lithium CR-2 type battery, Panasonic, Sanyo or equivalent
Transmission LED: Lights for 2 sec when reports alarm, alarm
restore or tamper events.
Battery Life Expectancy:
– For supervision signaling every 60 min - up to 10 years typical use.
– For supervision signaling every 15 min - up to 8 years typical use.
Battery Supervision: Automatic transmission of battery condition data
as part of any status report.
Operating Temperature (indoor): -20°C to 50°C (-4°F to 122°F).
Probe Operating Temperature (outdoor): -30°C to 70°C (-22°F to 158°F).
Storage Temperature (indoor): -20°C to 60°C (-4°F to 140°F).
Dimensions: 92 x 36.5 x 31 mm (3-5/8 x 1-7/16 x 1-1/4 in.).
Weight (excluding battery): 50 g (1.8 oz)
Compliance with Standards: CFR47 (FCC) part 15, ICES-003:04,
EN300220, EN301489, EN60950
This device complies with Part 15 of the FCC Rules and RSS-210 of
Industry and Science Canada. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including
interference that may cause undesired operation.
This device complies with the essential requirements and provisions of
Directive 1999/5/EC of the European Parliament and of the Council of
9 March 1999 on radio and telecommunications terminal equipment.
3. Preparation for Use
Follow the instructions in Figs. 2 and 3 showing how to open the
detector cover and gain access to the DIP switch.
A. Function Switches
The MCT-560 has a 4-position DIP switch function selector (Fig. 3) that
enables selection of up to 4 temperatures at which the detector will send
an alert. Each switch lever enables one temperature alert.
All switches are set to OFF, by default. Setting a switch to ON enables
the MCT-560 to detect the matched temperature as listed in Table 1.
Table 1. Alarm and restore conditions
Temp.
Application
point#
Temp rises
T1
Freezer fault
above -10
(14
Temp drops
T2
Freezing temp
below 7
sensing
(45°F)
Temp drops
T3
Cold temp
below 19
sensing
(
66
Temp rises
T4
Hot temp
above 35
sensing
(95°F)
Alarm condition
Restore condition
Threshold
Duration
Threshold
[min]
Temp drops
30
°
C
below -1
°F)
12°F)
(
Temp rises
10
°C
8°C
above
(46°F)
Temp rises
10
°C
above
20°C
°F)
(
8°F)
6
Temp drops
10
°C
below 3
(93°F)
Duration
[min]
10
C
10
10
10
4°C
1

Advertisement

loading

Summary of Contents for Visonic MCT-560

  • Page 1 There are a total of four fixed temperature points and the user can RFI protection: >20 V/m 80 to 2000 MHz enable one or more temperature point. The MCT-560 can be used in Temperature measurement accuracy (internal sensor or optional instances where temperature detection is critical.
  • Page 2: Miscellaneous Comments

    é enviada uma mensagem de restauração. O MCT-560 detecta as temperaturas no interior e no exterior do local de Existem quatro níveis de temperatura definidos e o utilizador pode instalação. O detector monitoriza a temperatura interior utilizando um escolher um ou mais níveis de temperatura.
  • Page 3 No caso de instalações exteriores, a sonda de temperatura é instalada no exterior, enquanto que o detector é instalado no interior. O MCT-560 tem 4 microinterruptores (Fig. 3) que permitem a escolha Em presença de uma situação de alarme, o código de identificação do de até...
  • Page 4: Especificaciones

    MCT-560 e o painel de GARANTIA A Visonic td., as Subsidiárias, Filiais e Distribuidores (“O Fabricante”) garante que os seus produtos O fabricante não assegura que o seu produto não possa ser comprometido ou falsificado ou que o designados daqui para a frente como “O Produto”...
  • Page 5: Preparación Para Su Uso

    Monte el soporte en la zona a monitorizar tan próximo como sea posible a panel PowerMax para asegurar la optima recepción de El MCT-560 tiene un DIP switch con un selector de 4 posiciones (Fig. 3) señal RF. que permiten la selección de hasta 4 temperaturas a las cuales el Si los dos terminales de sonda están cortocircuitados...
  • Page 6 VISONIC LTD. (UK): 7 COPPERHOUSE COURT, CALDECOTTE, MILTON KEYNES. MK7 8NL. TEL: (0870) 7300800 FAX: (0870) 7300801 VISONIC IBERICA SEGURIDAD, SL: C/ ISLA DE PALMA, 32 - NAVE 7, POLÍGONO INDUSTRIAL NORTE, 28700 SAN SEBASTIÁN DE LOS REYES, (MADRID), www.visonic-iberica.es ESPAÑA TEL (34) 91659-3120, FAX (34)