Accessory parts and Parts to be procured locally

H Accessory parts
Part name
Installation Manual
Heat insulating pipe
Washer
<Separate sold parts>
Part name
Standard wired remote controller
Refrigerant piping
• Piping material used for the conventional refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more thickness for Ø6.4, Ø9.5, Ø12.7.
Use copper pipe with 1.0 mm or more thickness for Ø15.9.
• Flare nut and flare works are also different from those of the conventional refrigerant.
Take out the flare nut attached to the indoor unit of the air conditioner, and use it.
H Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4" thick 0.8mm)
MMD-AP0071BH to MMD-AP0181BH
(9.5mm (diam.), Nominal (diam.) 3/8" thick 0.8mm)
MMD-AP0241BH to MMD-AP0561BH
Connecting pipe (Gas side)
(9.5mm (diam.), Nominal (diam.) 3/8" thick 0.8mm)
MMD-AP0071BH to MMD-AP0121BH
(12.7mm (diam.), Nominal (diam.) 1/2" thick 0.8mm)
MMD-AP0151BH to MMD-AP0181BH
(15.9mm (diam.), Nominal (diam.) 5/8" thick 1.0mm)
MMD-AP0241BH to MMD-AP0561BH
Power supply cord
2
Cable 3-core 2.5mm
,
in conformity with Design 60245 IEC57
Q'ty
Shape
1
This manual
2
8
M10 × Ø34
Q'ty
Shape
1
• In this air conditioner, a Direct current motor is
3
Usage
(Be sure to hand over to customers)
For heat insulation of pipe connecting section
For hanging-up unit
Usage
Model: RBC-AMT21E
INFORMATION
adopted for the indoor fan motor.
The current limit control works in the
characteristics of direct current motor.
When exchanging a high-performance filter with
new one or opening the service board, be sure to
stop the fan; otherwise a protective control works
resulted in stop of the air conditioner, and then
an error code [P12] may be output.
However it is not a trouble.
After the desired operation has finished, reset the
earth leak breaker of the indoor unit and push the
operation STOP button on the remote controller
to return the operation to the usual operation.