6. Connecting the M-NET Interface, the Power Supply, and the ME Remote Controller

• When connecting the unit to a system controller or ME Remote Controller, connect the transmission line of the M-NET to the
control signal terminal.
Connect the 2-core connection wrings A to A1/B1 or A2/B2 (they can be connected to either).
• Cross the shield portion of each connecting wire using the S terminal only when cross wiring the connection wires.
• When connecting the connection wrings A and the ME Remote Controller connection wrings B to the terminal board, there is
no need to worry about polarity.
When the connection wrings A are not cross-wired
A1 B1 A2 B2
2
• After completing the wiring, securely affix a cord clamp to each electrical wire.
1
1 Screws
2 Cord clamp (large)
3 Cut with nippers at the notches.
Make sure the cut surface is free of any burr so that the
connection wire dose not get damaged.
Caution
• Electrical work should be performed in accordance with the Technical Standards Regarding Electrical Equipment
and the Interior Wiring Standards.
• Connection wiring and remote control wiring should be located as far away from other electrical wiring as possible.
Placing them too closely together could cause a malfunction.
When the connection wrings A are cross-wired
S
3
2
A1 B1 A2 B2
S
2
3
When the connection wrings
1
1 Shield
2 Connection wirings A
(M-NET transmission wire)
3 ME Remote Controller
(only when needed)
1
2
Bare wire size
A
are cross-wired
2
1
3
7