Lumel S4AI User Manual

Lumel S4AI User Manual

Module of analog inputs
Hide thumbs Also See for S4AI:

Advertisement

Quick Links

MODULE OF ANALOG INPUTS
S4AI
USER'S MANUAL
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S4AI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Lumel S4AI

  • Page 1 MODULE OF ANALOG INPUTS S4AI USER’S MANUAL...
  • Page 2: Table Of Contents

    6. DIGITAL INTERFACES ......................... 20 6.1 RS485 interface - parameter list ..................20 6.2 USB interface - parameter list .................... 20 6.3 Map of S4AI module registers .................... 21 7. BEFORE YOU NOTIFY OF A DEFECT ..................30 8. SOFTWARE UPDATE ........................31 9.
  • Page 3: Application

    User Manual 1. APPLICATION S4AI module is designed to measure the standard signal (voltage, current, temperature, resistance, etc.) and to provide the measured values in a digital form via the MODBUS protocol. Input signals are divided into two groups of two inputs which are insulated with each other. RS485 interface and USB are isolated from the input, output signals and from the power supply.
  • Page 4: Basic Requirements, Operational Safety

    S4AI-07 User Manual 3. BASIC REQUIREMENTS, OPERATIONAL SAFETY Meaning of the symbols used in this manual: Warning! Warning of potentially dangerous situations. It is especially important to read and understand these instructions before connecting the device. Failure to meet the instructions marked with this symbol can result in a serious injury of personnel and damage to the device.
  • Page 5: Installation

    S4AI-07 User Manual 4. INSTALLATION 4.1. Installation The RE62 controller is adapted for installation in a modular installation switchgears on a 35 mm support rail. The housing is made of plastic. Housing dimensions are 53 x 110 x 60.5 mm. Detachable terminal blocks located outside the module allow for connection of power supply, RS482 interface and outputs, with conductors of cross section up to 2.5 mm...
  • Page 6: External Connections Diagram

    Connections the module are shown in Fig. 3. In the event when the module is powered with DC voltage, the voltage polarity does not matter. Alarm output Power supply ON/ERROR LED USB Port Fig. 3: Electrical connections of S4AI module a) with ±10 V, ±20 mA inputs b) with Pt100, Pt500, Pt1000 inputs, JKS, ±150 mV thermocouples...
  • Page 7 300 V insulation INPUT 1 INPUT 3 INPUT 2 INPUT 4 50 V insulation Fig. 4: Schematics of S4AI module insulation Table 1: the meaning of LED signaling Description ON / ERROR - continuous green: normal operation, (green / red) - alternating green/red flashes: error or range exceeding of one or more active inputs.
  • Page 8: Side Bus

    19, 20 and 21 are connected to the same RS485 interface. When the caps are broken, S4AI module may be connected to other LUMEL devices equipped a side bus. In this way, many S4AI modules can create a multi-channel block of analog inputs.
  • Page 9: Operation

    RS485: the interface must be configured (registers 4004..4007) and the device must be powered on. 5.2 RS485 Modbus Slave To use the S4AI module as a MODBUS SLAVE device on RS485 interface, the device must be configured as follows: ...
  • Page 10: Virtual Channels

    Example of configuration: shunt with rated current 4A was connected. At rated current the voltage at the shunt is 150mV. To enable S4AI module calculation of the direct current flowing through the shunt, the individual characteristics should be set as follows: ...
  • Page 11: Auto-Compensation

    S4AI-07 User Manual  '2': AVG – calculation of the average value of all the analog inputs assigned to the function,  '3': MIN – selection of minimum value of all the analog inputs assigned to the function,  '4': MAX – selection of maximum value of all the analog inputs assigned to the function, ...
  • Page 12: Timers

    S4AI-07 User Manual 5.6 Timers Each analog input with individual characteristics and each virtual channel is monitored by 2 timers: the first one counts seconds up when the monitored input or virtual channel reaches a value greater than a defined threshold,...
  • Page 13: Alarms

    S4AI-07 User Manual .7 Alarms S4AI module is equipped with two alarm outputs, which can be configured as follows:  select the monitored input (registers 4009, 4014)  select the operating mode of the alarm output (registers 4010, 4015) as shown in Figure 9, ...
  • Page 14: Module Configuration With E-Con Software

    5.8 Module configuration with E-Con software Fig 11: Window of E-Con software S4AI module can be configured using the E-Con software. This program is a free application available from the manufacturer’s website (www.lumel.com.pl). The module must be connected to a PC via USB or RS485 interface.
  • Page 15: Configuration Parameters

    S4AI-07 User Manual When connected via the RS485 interface, set the following transmission parameters: the address (device ID), the speed and mode. Factory settings of RS485 interface are as follows: Address 1, speed 9600, mode RTU 8N2. For USB connection the following must be set: address 1 (or any other), speed 115200, mode RTU 8N2.
  • Page 16 S4AI-07 User Manual Tabs Input 1, 2, 3, 4 configuration Version S4AI-1xxxxx: Disabled ±10 V ±20 mA Version S4AI-2xxxxx: Disabled Measuring input type Selecting the type of signal fed to the input Disabled PT100 PT500 PT1000 ±150 mV Thermocouple J...
  • Page 17 S4AI-07 User Manual *) for virtual channel 2 only Not used Analog input 1 Analog input 2 Analog input 3 Selection of input engaged in the performance of Argument 4 Not used Analog input 4 mathematical function. See point 5.4.
  • Page 18 S4AI-07 User Manual - upper overrun for inputs - lower overrun for inputs - errors See point 5.8.2. Deleting an alarm indication when the option of alarm Delete alarms indication indication after its stop is enabled. Deleting the minimum and maximum values for all...
  • Page 19: S4Ai Module Status

    S4AI-07 User Manual 5.8.2 S4AI module status Fig 14: Preview of S4AI module status in e-Con program. 5.8.3 Measured values Fig 15: Preview of measured values in e-Con program. 5.8.4 Values of the timers Fig 16: Preview and reset of upper and lower thresholds overruns duration timers in e-Con program.
  • Page 20: Digital Interfaces

    - 17 device identification Transmission factory settings: address 1, baud rate 9.6 kbit/s, mode 8N2. Broadcast address: 253 6.2 USB interface - parameter list The USB interface is dedicated only to S4AI module configuration.  ID 219 (0xDB)  device address ...
  • Page 21: Map Of S4Ai Module Registers

    User Manual 6.3 Map of S4AI module registers In S4AI module the data is placed in 16- and 32-bit registers. Process variables and operating parameters of the module are placed in the areas of register groups depending on the type of the variable. The values of the 16-bit registers are arranged in the order from the least significant bit to the most significant bit (b0-b15).
  • Page 22 S4AI-07 User Manual 3 – unavailable / PT1000 4 – unavailable / ±150 mV 5 – unavailable / Thermocouple J 6 – unavailable / Thermocouple K 7 – unavailable / Thermocouple S Input type 3: 0 - off 1 – ±10V / PT100, 2 –...
  • Page 23 S4AI-07 User Manual Delay of deactivation of alarm 1 (s): The time that must elapse from the alarm condition till 4012 0...3600 the alarm deactivation. 0 – no delay Maintaining the signaling of alarm 1: The alarm is indicated also after the it is stopped (does 4013 0...1...
  • Page 24 S4AI-07 User Manual Enabling individual characteristics for input 4 (see point 5.3): 4026 0...1 0 – characteristics disabled 1 – characteristics enabled 5, 10, 30, 50, Time constant of the digital filter on input 1 in units of 4027 100, 150, 200 0.1 second (5 = 0.5 s)
  • Page 25 Special order version (read-only): Version of the module (read-only): 0 – S4AI-1-X-XX-X-X ±10 V - ±20 mA 4040 1 – S4AI-2-X-XX-X-X Pt100 - Pt500 - Pt1000 - ±150 mV shunt - thermocouple J,K,S 4041 Older word of the serial number.
  • Page 26 S4AI-07 User Manual 6 – division Virtual channel 1, the second argument for multiplying 4048 -30000...30000 or dividing (x10) Virtual channel 2, mathematical function – argument 1: 0 – not used, 1 – input 1, 2 – input 2, 4049 0...5...
  • Page 27 S4AI-07 User Manual Table 5: Module measurement registers Address of Description Address of 16-bit Access 32-bit registers mode registers 6600 6800 7500 Measurement at input 1 (channel 1), without individual characteristic 6602 6802 7501 Measurement at input 1 (channel 2), without individual characteristic...
  • Page 28 S4AI-07 User Manual 6708 6908 7554 Upper overrun timer of virtual channel 1 6710 6910 7555 Lower overrun timer of virtual channel 1 6712 6912 7556 Upper overrun timer of virtual channel 2 6714 6914 7557 Lower overrun timer of virtual channel 2...
  • Page 29 S4AI-07 User Manual Table 6: Float type configuration registers Address of Address of 16- Access 32-bit Description bit registers mode registers 6000 6200 8000 AL_L 1: Low threshold of alarm 1 triggering 6002 6202 8001 AL_H 1: High threshold of alarm 1 triggering...
  • Page 30: Before You Notify Of A Defect

    S4AI-07 User Manual 7. BEFORE YOU NOTIFY OF A DEFECT In the case of improper operation of the module, verify the fault in the following table: Table 7: Description of error Symptom Procedure Remarks ON / ERROR LED is not...
  • Page 31: Software Update

    Then select Firmware Update on the right side of the program menu. LUMEL UPDATER (LU) will be launched (Fig. 17). S4AI module is supported by LU from version 2.01. Select the device (S4AI) in the program, the port on which the device is installed in Windows, set the appropriate transmission parameters (115200, 8n2) in the access window under Setup, and indicate the update file.
  • Page 32: Technical Data

    Send button. LU will show the progress bar indicating the percentage and throughout the update ON/ERROR LED on S4AI module will blink in green. After the update the module will restart, restore factory parameters and start normal operation. LU message box will display Done and the module update duration.
  • Page 33 S4AI-07 User Manual K type thermocouple input: range of measure temperature: -250 °C…1372 °C basic error: 0.1 % of the range S type thermocouple input: range of measure temperature: -50 °C…1768 °C basic error: 0.1 % of the range Additional errors: ...
  • Page 34 S4AI-07 User Manual maximum length of USB cable: Test voltage: 2210 V a.c. rms 1 minute between housing / power supply and: - RS485 - binary outputs - USB - analog inputs 1390 V a.c. rms 1 minute between: - analog inputs / RS485...
  • Page 35 S4AI-07 User Manual  installation category III,  degree of pollution  maximum voltage relative to earth: - for power circuit 300 V - for other circuits 50 V  altitude < 2000 m...
  • Page 36: Ordering Codes

    S4AI-07 User Manual 10. ORDERING CODES Table 8: Ordering code ANALOG INPUT MODULE S4AI - Inputs: 4 programmable analog inputs: ±10 V - ±20 mA 4 programmable analog inputs: Pt100, Pt500, Pt1000, J, K, S, ±150 mV According to the agreement with the customer* Power supply: 85...253 V a.c.
  • Page 37 S4AI-07 User Manual AVAILABLE ACCESSORIES: Accessories: the following accessories can be ordered together with input module S4AI:  USB cable A/miniUSB-B - 1m black; order code 20-069-00-00150,  modular connector of internal RS485 bus; order code 24-171-01-00016,  transition connector from internal RS485 bus to cable connector; order code 24-171-01-...
  • Page 38 LUMEL S.A. ul. Sulechowska 1, 65-022 Zielona Góra, POLAND tel.: +48 68 45 75 100, fax +48 68 45 75 508 www.lumel.com.pl Export department: tel.: (+48 68) 45 75 139, 45 75 233, 45 75 321, 45 75 386 fax.: (+48 68) 32 54 091...