Fans

The lifespan of the cooling fan depends on the running time of the fan, ambient
temperature and dust concentration. See the firmware manuals for the actual signal which
indicates the running time of the cooling fan. For resetting the running time signal after a
fan replacement, contact ABB. Replacement fans are available from ABB. Do not use
other than ABB specified spare parts.

Replacing the cooling fan of the supply module (frame D7T)

The fan replacement procedure is the same for both the standard speed-controlled cooling
fan and direct-on-line fan (option +C188) of the D7T module.
WARNING! Only qualified electricians are allowed to do the work described
below. Read the complete safety instructions given in Safety instructions for
ACS880 multidrive cabinets and modules (3AUA0000102301 [English]) before
you service the drive. Ignoring the instructions can cause physical injury or death, or
damage to the equipment.
WARNING! Wear protective gloves and long sleeves! Some parts have sharp
edges.
1. Stop the drive and disconnect it from the AC power line. Obey the instructions in
section
Electrical safety precautions
2. Open the cubicle door.
3. Remove the screws holding the front cover plate (a) and remove the cover.
4. Disconnect the fan wiring from the supply module (both the power supply plug and the
fiber optic control wiring).
5. Support the fan holder (b) from below and pull it to release it from the module.
6. Pull out the fan holder.
7. Transfer the fan control box (c) from the old fan holder to the new fan holder.
8. Install a new fan in reverse order.